Installation & Operation Manual
29
6
Hydronic piping
(continued)
Figure 6-2
Pressure Drop vs. Flow - Models 50 - 210
20°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
50
5.1
11
1"
UP26-96F/
UPS26-99F
0011
NRF-36
E7
80
7.5
24
1"
UP26-96F/
UPS26-99F
0011
NRF-36
E7
105
9.8
27
1"
UPS26-99F
0013
NRF-36
E11
150
14.0
20
1"
UPS26-99F
0011
NRF-36
E7
210
19.6
29
1"
UPS32-160
1400-50
PL-55
E9
Table 6A
Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
25°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
50
4.1
7.3
1"
UPS15-58FC
0014
PL-30/NRF-36
E7
80
5.9
15.0
1"
UPS15-58FC
0014
PL-30/NRF-36
E7
105
7.7
17.5
1"
UP26-64F/
UPS26-99F
0014
PL-30/NRF-36
E7
150
11.0
12.8
1"
UP26-64F/
UPS26-99F
0014
PL-30/NRF-36
E7
210
15.5
19.0
1"
UP26-99F/
UPS26-99F
0013
PL-36/NRF-36
E7
35°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
50
2.9
4.1
1"
UPS15-58FC
007
NRF-22
Astro-30
80
4.2
7.3
1"
UPS15-58FC
007
NRF-22
Astro-30
105
5.5
9.8
1"
UPS15-58FC
007
NRF-22
Astro-30
150
7.9
10
1"
UPS15-58FC
008/0010
PL-30/NRF-36
Astro-30
210
11.0
10.1
1"
UPS15-58FC
0010
PL-30/NRF-36
Astro-50
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude
models.
NOTICE
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude
models.
NOTICE
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of
elevation.
NOTICE