ProLine P16800
6
1.4 Functional Safety (Optional)
The P16800 decouples signals from safety-related signal circuits without influencing them. The input
signal is transmitted to the output signal with the specified accuracy in a functionally safe manner.
The nameplates on the products clearly specify the product properties.
SRAC – Safety Related Application Conditions
The information regarding use of the P16800 and the conditions of use specified in this User Manual
are to be followed as safety-related application conditions (SRACs) in order to achieve the specified
functional safety characteristics regarding absence of interaction and signal transmission. The rein-
forced insulation of the SIL product between input and output and the specified limits for altitude,
overvoltage category, and working voltage must be observed.
Absence of Interaction EN 50129: SIL 4
• FFR: 1.9 FIT, per channel at 50 °C (122 °F)
• Voltage input: R > 60 kΩ, I < 100 μA
• Current input: U < 1 V
• Electrical isolation as specified.
Signal Transmission EN 50129: SIL 2
• FFR: 94 FIT, per channel at 50 °C (122 °F)
• Signal transmission within specifications
1.5 Installation and Operation
All national and local regulations relating to the installation and operation of the product in force at
the destination must be followed.
All connected current or voltage circuits must meet the SELV, PELV, or Area I requirements according to
EN 50153.
• The product must be installed by qualified electrical engineering personnel.
• The product may not be opened, modified, or independently repaired. but replace it with an
equivalent product. Repairs may only be carried out by Knick.
• The operating company must ensure compliance with the specified interface parameters and
ambient conditions.
• The product must be installed in a lockable control cabinet.
See also
1.6 Disposal
The local codes and regulations must be observed when disposing of the product.