Commissioning functions
Balancing airflow
30
Measure and enter
the actual
minimum
secondary airflow
The display begins flashing
SMIN
and also displays the actual airflow
at the bottom.
Note:
The airflow displayed by the
STE-8000 in this step is the actual,
uncorrected airflow.
1. Wait for the minimum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display.
SMIN
stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
advances to
SEC
.
Advance or exit
1. Press the or buttons to select
one of the following
•
PRI
to balance the primary VAV
for dual duct systems
•
BACK
to choose another
commissioning function
•
EXIT
to return to the temperature
display.
2. Press the button to select the next
function.
The airflow balancing procedure (Continued)
Procedure
Steps
STE display
Set
Point
Set
Point
SMIN
OO
Set
Point
SEC