STE-8001 and STE-8201 sensors
Revision A
Commissioning functions
Box options
17
Set the mode of
reheat for the
terminal unit
1. Press the or buttons to choose
one of the following reheat options.
None
—Reheat is not enabled.
Staged
—Enables two or three stage
reheat. If lighting is enabled the
staged reheat is set to two stages. If
lighting is not enabled, three reheat
stages are available.
Modulating
—The reheat output
varies from 0-10 volts.
Floating
—The reheat outputs control
a tristate actuator.
Time proportional
—Controls a
thermal wax valve with a 24-volt
triac output.
2. Press the button to save the reheat
option and advance to the next
function.
Set the fan option
1. Press the or buttons to choose
one of the following fan options.
None
—No fan is connected to the
controller.
Series
—The VAV unit includes a
series fan.
Parallel
—The VAV unit includes a
parallel fan.
2. Press the button to save the fan
option and advance to the next
function.
Procedure to set the box functions (Continued)
Procedure
Steps
STE display
Set
Point
NONE
REHT
Set
Point
NONE
FAN