background image

KMC Controls

KMD–1162 Installation and Operation

4

Models

Almond

KMD-1162-10

White

KMD-1162W10

Network Cable Preparation

Connecting a NetSensor to a KMC controller requires a six-wire cable 
with RJ-12 connectors on each end. Use either the KMC Controls 
ready-to-use cables or make cables to length when the NetSensor is 
installed. Cables made to length must meet the following 
requirements:

Cable length is no longer than 75 feet (22.9 meters).

Use cable with #24 AWG size conductors.

Cable insulation must meet local building codes. Plenum rated 
cable is recommended.

Connectors are appropriate for the cable in use and are installed 
following the connector manufactures instructions.

Cable Details

RJ-12

Summary of Contents for NetSensor KMD-1162

Page 1: ...llation and Operation Guide NetSensor KMD 1162 Temperature sensor Contents Specifications 2 Network Cable Preparation 4 Rough in preparation 5 Installing the NetSensor 5 Operation 6 Maintenance 7 903 019 03A Revision A ...

Page 2: ...length Maximum 75 feet 22 9 meters PC port Four pin connector for service connection to software tools Power 5 volts DC supplied by connected controller Mounting Surface mount directly to any flat surface or to a 2 x 4 inch or 4 x 4 inch handy box Mounting on a 4 x 4 inch box requires a mounting backplate Weight 2 8 ounces 80 grams Material Light almond or white plastic Environmental Limits Shippi...

Page 3: ...eters KMD 5690 50 feet 15 2 meters KMD 5691 75 feet 22 9 meters KMD 5692 Interface Cable KMD 5624 Gasket HPO 1161 Sensor type and accuracy Type 10k thermistor Accuracy 2 F 1 1 C Operating range 47 to 97 F 8 to 36 C Dimensions A B C D E 3 25 in 5 16 in 2 58 in 3 25 in 0 87 in 83 mm 116 mm 66 mm 83 mm 22 mm A C D E B ...

Page 4: ...trols ready to use cables or make cables to length when the NetSensor is installed Cables made to length must meet the following requirements Cable length is no longer than 75 feet 22 9 meters Use cable with 24 AWG size conductors Cable insulation must meet local building codes Plenum rated cable is recommended Connectors are appropriate for the cable in use and are installed following the connect...

Page 5: ...numbers Caution To prevent mounting screw heads from touching the circuit board in the NetSensor use only the mounting screws supplied by KMC Controls Using screws other than the type supplied will damage the NetSensor Installing the NetSensor 1 Turn the Allen screws in the base of the NetSensor clockwise until they clear the cover Swing the sensor away from the backplate to remove it 2 Route the ...

Page 6: ...on The following sections describe the controls and indicators found on the NetSensor Display The display includes two 7 segment LCD digits that are visible across a normal size office Room temperature is displayed until either setpoint button is pressed and then the display changes to setpoint mode If the temperature remains out of the temperature operating range for more than 45 seconds the KMD ...

Page 7: ...s increments or decrements the setpoint temperature by one degree Fahrenheit Backlight When either setpoint button is pressed the backlight turns on and remains on for 10 seconds after the last button is released Programming instructions Programming instructions for NetSensors are included in Help supplied with WinControlXL BACstage and TotalControl Maintenance Remove dust as necessary from holes ...

Page 8: ...e in any form by any means without the written permission of KMC Controls Inc Printed in U S A Disclaimer The material in this manual is for information purposes only The contents and the product it describes are subject to change without notice KMC Controls Inc makes no representations or warranties with respect to this manual In no event shall KMC Controls Inc be liable for any damages direct or...

Reviews: