MEP-7xxx Direct-Coupled Actuators (up to 320 in-lb.)
10
Applications Guide, AN1113A Rev. D
Rotation in Wrong Direction
• For tri-state models, check the CW/CCW wiring.
• For proportional models, check the position of
the direction switch (Switch 2). See
.
• For fail-safe operation, check the Fail-Safe Direc-
tion switch. See
Stroke Range Is Wrong
• Use and/or check position of the HMO-4536
adjustable end stop kit.
• On proportional models, check the auto-map-
.
• Check the voltage from the controller or thermo-
stat.
Wiring Issues
• For master/slave wiring, see
• Check for correct wiring for the application.
• Check the wiring at the connected devices.
• Use a voltmeter and ohmmeter to check the
terminals for expected values.
• See
Tips for Connecting 24-Volt Power Applica
.
NOTE: Wiring must be adequate to avoid exces
-
sive voltage drop on long runs! Allow
plenty of “cushion” in measurements. A
meter may be too slow to register tran
-
sient dips or peaks during startup.