background image

KMC Controls, 19476 Industrial Drive, New Paris, IN 46553  

/

  877-444-5622  

/

  Fax: 574-831-5252  

/

  

www.kmccontrols.com

HPO-9001 Distribution Module

Installation Guide

For physical and ESD (ElectroStatic Discharge) 
protection

, the module board 

should be mounted 

inside a suitable enclosure

 using the supplied Snap 

Track (or track that is integrated into the enclosure). 
Complete the steps in the following sections to 
install the module.

NOTICE

OBSERVE PRECAUTIONS 

FOR HANDLING

ELECTROSTATIC

SENSITIVE DEVICES

MOUNT IN SNAP TRACK

1.  Install the (included) Snap Track 

1

 in an 

enclosure using the provided screws.

NOTE: 

When mounting in an enclosure, provide 
clearance for cables plugged into ports.

2.  Snap the HPO-9001 board into the Snap Track 

slots 

1

.

1

NOTE: 

If mounting in an 

HCO-1101

 enclosure, 

which has Snap Track integrated into its 
lower section, the Snap Track included 
with the HPO-9001 does not need to be 
installed. The HCO-1101 enclosure can 
mount on a flat surface (via screw holes) 
or on a DIN rail (via an integrated DIN rail 
channel).

NOTE: 

If protection from dust is also a 
factor, mount in a 

NEMA 1 (IP10)

 

rated enclosure such as an 

HCO-

1034/1035/1036

.

INTRODUCTION

The HPO-9001 Distribution Module allows up to 

eight

 STE-9000 series 

NetSensors

 (with firmware 

version R5.1.0.10 or later installed) to be linked to 
one BAC-5900/9000/9300 series controller (with 
firmware version R1.2.0.9 or later installed). The 
module provides power (from a connected 24 VAC 
transformer) and addressing (according to the 
connected port) for each NetSensor.
Alternately, it allows 

one

 

STE-6010/6014/6017

 

analog temperature sensor to be connected to a 
controller along with up to 

seven NetSensors

.

NOTE:  Applications require custom 

configuration and programming

. See 

Configuration and Programming on 
page 3

.

The module may be connected to a controller with 
a standard (Category 5 or better) Ethernet patch 
cable up to 150 feet (45 meters) long. Cables from 
the module to any NetSensors may also be up to 
150 feet (45 meters) long. See 

Accessories and 

Replacement Parts on page 5

.

NOTE: 

For module specifications, see that 
section in the 

Conquest STE-9000 

NetSensor 

data sheet on the web at 

kmccontrols.com

.

CONTENTS

Introduction .............................................. 1
Mount in Snap Track ................................... 1
Connect Controller ..................................... 2
Connect Sensors ........................................ 2
Connect Power .......................................... 2
Configuration and Programming ................... 3
Sample Applications ................................... 4
Active NetSensor Determination ................... 4
Troubleshooting ........................................ 4
Accessories and Replacement Parts ............. 5
Important Notices ...................................... 5