background image

CSP-4702 

    3 

Installation Guide

Operation Test

To test the CSP-4702 operation:
1.  Temporarily disconnect the thermostat signal 

wire leading to the “2–10 IN” terminal.

2.  Jumper the “2–10 IN” terminal to the “16 VDC 

OUT” terminal. The green Open LED should 

illuminate, and the shaft drive hub should start 

rotating the damper open. The damper should 

go to full open unless the maximum limit was 

set at the CSP-4702, and then the damper will 

only go to the maximum setting. If the damper is 

rotating closed, change the direction jumper. (See 

Rotation Direction on page 2

.)

3.  Remove any jumper to the “2–10 IN” terminal. 

If

 there is a normal amount of airflow in the 

duct at the time (creating a differential pressure 

exceeding the minimum limit), the red Close LED 

should illuminate, and the shaft drive hub should 

be rotating the damper closed. The damper 

should go to full closed unless the minimum limit 

was set at the CSP-4702, and then the damper will 

only go to the minimum setting. If the damper 

is rotating open, change the rotation direction 

jumper. (See 

Rotation Direction on page 2

.)

4.  Reconnect the thermostat signal wire to the “2–10 

IN” terminal.

5.  Adjust the thermostat’s setpoint all the way up 

(simulating a drop in temperature and a need for 

less cooling or more heating) and then all the way 

down (simulating a rise in temperature and a 

need for more cooling or less heating) and check 

that the damper position reacts accordingly.

Min. and Max. Flow Limits

NOTE:

  If desired, the min. and max. limits can 

be set within the thermostat 

or

 the CSP-

4702, but 

do NOT try to set the limits at 

BOTH the controller and the thermostat 

(or else the limits will not reflect either the 

controller’s or the thermostat’s limits).

Limits Set at the CSP-4702

To set the minimum and maximum flow limits at the 

CSP-4702 

(with thermostat supplying 2–10 VDC)

:

1.  Ensure the thermostat output is 2–10 VDC. 

For 

the CTE-5202 thermostat, see the 

CTE-5202 

Applications Guide

.

2.  Loosen the screw on the conduit fitting and lift up 

to remove the fitting.

3.  Connect a voltmeter to the meter taps. The 

middle pin (REF) is the common for the outer 

(MIN and MAX) pins.

4.  Adjust the MIN potentiometer for the desired 

minimum voltage. The factory default is 0 VDC = 

0" wc.

NOTE:

  1 VDC = 1" wc. If, for example, the desired 

minimum is 0.5" wc, set the voltage for 0.5 

VDC.

5.   Adjust the MA X potentiometer to the desired 

maximum voltage. The factory default is 2 VDC = 

2" wc.

NOTE:

  If, for example, the desired maximum is 1.5" 

wc, set the voltage for 1.5 VDC.

6.  Reinstall the conduit fitting and tighten the screw.

Limits Set at the Thermostat

To set the flow limits at the thermostat 

(with CSP-

4702 potentiometers set at their defaults)

:

1.  Return the CSP-4702 potentiometers to the factory 

defaults if necessary (see above).

2.  Set the thermostat output limits according to its 

instructions. For the CTE-5202 thermostat, see the 

CTE-5202 Applications Guide

.

NOTE:

  Voltage from the thermostat = 

desired ΔP 

x (voltage span = 8 VDC)/(pressure span = 

2" wc) + 2 VDC.

 For example, if a minimum 

of 0.1" is desired instead of the default 0", 

then 0.1 x 4 + 2 (= 0.4 + 2) = 2.4 VDC for the 

minimum limit. If a maximum of 1.9" is 

desired instead of the default 2", then 1.9 x 

4 + 2 (= 7.6 + 2) = 9.6 VDC for the maximum 

limit.

LIMITS

0-2 VDC / 0-2"H2O

MIN REF MAX

Illustration 4—CSP-4702 Limits Adjustment

Maintenance

No routine maintenance is required. The motors 

are permanently lubricated and all internal gear-

train components are oil-impregnated. Careful 

installation will also ensure long term reliability and 

performance.

Summary of Contents for CSP-4702

Page 1: ...Crank Arm Kit NOTE For VAV applications with the analog CTE 5202 thermostat see the CTE 5202 Applications Guide For static pressure controller applications see the CSP 4702 Static Pressure Bypass Control Application Guide The CSP 4702 mounts directly to 1 4 to 5 8 inch 6 to 16 mm round shafts or 1 4 to 7 16 inch 6 to 11 mm square shafts 1 Ensure the damper can move freely through its entire range ...

Page 2: ... see the CSP 4702 Static Pressure Bypass Control Application Guide NOTE For VAV applications the SSS 1000 series differential pressure flow sensor must be mounted with the arrow pointing in the direction of the air flow To connect to 1 4 inch tubing from the CSP 4702 an SSS 100x differential pressure flow sensor requires a 3 8 to 1 4 barb union adapter and 1 of 3 8 OD x 0 062 FR tubing for both co...

Page 3: ...ect either the controller s or the thermostat s limits Limits Set at the CSP 4702 To set the minimum and maximum flow limits at the CSP 4702 with thermostat supplying 2 10 VDC 1 Ensure the thermostat output is 2 10 VDC For the CTE 5202 thermostat see the CTE 5202 Applications Guide 2 Loosen the screw on the conduit fitting and lift up to remove the fitting 3 Connect a voltmeter to the meter taps T...

Page 4: ...sition See Rotation Direction on page 2 Check the polarity and level of the input signal from the thermostat Wrong Rotation Direction or Stroke Range Check the position of the direction jumper See Rotation Direction on page 2 Check the flow limits on the controller and the thermostat See Min and Max Flow Limits on page 3 Check the adjustable stop position No Pressure Output Signal Check the wiring...

Reviews: