background image

CSC-3000 Series Pneumatic VAV Reset Volume Controllers 

    7 

Applications Guide, Rev G

Troubleshooting

NOTE:  The controller should be set according 

to the specifications found on the 

manufacturer’s label on the VAV box.

NOTE:  The CSC-3000 series are position sensitive. 

Be sure to mount the controller with 

the correct orientation. See 

Mounting on 

page 2

. If the controller is calibrated in a 

position other than the final mounting 

position, the calibration (minimum and 

maximum flow limits) will be off.

NOTE:  These controllers are typically used on 

single-duct applications but may be 

found in dual-duct applications. (See, for 

example, 

Dual Duct on page 13

 and 

Dual 

Duct, Constant Volume on page 14

.) When 

working on dual-duct applications it may 

be necessary to work on one duct at a time.

Troubleshooting issues to consider include:
•  Is there an adequate main air (M) supply?
•  Is there adequate upstream system (duct) air?
•  Is the application correct and piped correctly? 

See 

Connections on page 3

, 

Determining the Type 

of Reset on page 4

, and 

Applications on page 10

.

•  Is the damper action (NC/NO) set correctly? Do 

the damper’s and controller’s action match? See 

Damper Action on page 4

.

•  Is the damper binding? Will the actuator drive 

the damper full open to full close? (Sufficient 

main air is required to provide the actuator with 

enough force to operate the damper/linkage.) Is 

the actuator leaking? (Even small leaks can cause 

the actuator to not stroke. You can test for leaks 

with a squeeze bulb to ensure there are no leaks 

at the actuator diaphragm or fittings.)

•  Does the thermostat send an adequate signal to 

the controller?

•  Are LO STAT and HI STAT set correctly for the 

thermostat action? When cycled, can the control-

ler repeat the LO STAT and HI STAT settings? If 

the LO STAT or HI STAT must be set for “0” wc, 

see the notes about 

zero minimum

 in 

DIRECT 

Reset Minimum and Maximum on page 4

 or 

RE-

VERSE Reset Minimum and Maximum on page 5

.

Maintenance

No routine maintenance is required. Each compo-

nent is designed and manufactured for reliability 

and performance. Careful installation and use will 

ensure long-term dependability.

 CAUTION

Pneumatic devices must be supplied with clean, 
dry control air. Any other medium (e.g., oil 
or moisture contamination) will result in the 
device’s eventual failure.

•  Is the airflow pickup properly placed, and does it 

send a good differential pressure to the control-

ler? (See 

Connections on page 3

.)  Is the airflow 

sensor dirty or defective? (Disconnect the sensor 

from the controller before attempting to blow the 

sensor clean!)

•  Are reset start and reset span set correctly? See 

Reset Start Point on page 6

 and 

Reset Span on 

page 6

.

Important Notices

The KMC logo is a registered trademark of KMC 

Controls, Inc. All rights reserved. No part of this 

publication may be reproduced, transmitted, tran-

scribed, stored in a retrieval system, or translated 

into any language in any form by any means with-

out the written permission of KMC Controls, Inc.
The material in this document is for information 

purposes only. 

The contents and the product it de-

scribes are subject to change without notice.

 KMC 

Controls, Inc. makes no representations or warran-

ties with respect to this document. In no event shall 

KMC Controls, Inc. be liable for any damages, direct 

or incidental, arising out of or related to the use of 

this document.

Summary of Contents for CSC 3000 Series

Page 1: ... 4 REVERSE Reset Minimum and Maximum 5 Reset Start Point 6 Reset Span 6 Troubleshooting 7 Maintenance 7 Important Notices 7 Magnehelic Gauge to Airflow Rate Chart 8 Replacement Cross References 9 Applications 10 Cooling 10 Cooling with Heating Valve 11 Cooling with Heating P E Switch 12 Dual Duct 13 Dual Duct Constant Volume 14 Index 15 NOTE This Application Guide does not apply completely to the ...

Page 2: ...w These CSC 3000 series reset volume controllers are designed for use on heating or cooling systems with normally open or normally closed VAV terminal units and direct or reverse acting thermostats They are sub master air velocity controllers Each is equipped with separate adjustment knobs for mini mum and maximum airflow setpoints Models are available with various reset start points A master cont...

Page 3: ...ack to undamaged material and reconnect Replace the tubing if it is brittle or discolored CAUTION Pneumatic devices must be supplied with clean dry control air Any other medium e g oil or moisture contamination will cause the device to fail NOTE You can easily test for leaks with a squeeze bulb to ensure there are no leaks at the actuator diaphragm or fittings 7 Use a flow hood or tee a Magnehelic...

Page 4: ... Direct Reset DA thermostat for cooling or RA thermostat for heating perform the following steps 1a On the CSC 3000 disconnect the T port and leave it open Temporarily plug the tubing but do NOT plug the port 1b Alternately instead of removing the tubing from the T port temporarily remove the plug from the CSC 3000 s G port 2 Adjust the LO STAT P center dial one adjustment at a time until the desi...

Page 5: ...just the dial no more than about a half rotation at a time After making any adjustment wait approximately ten seconds while watching for motion in the damper shaft If no motion occurs make the next adjustment 3a Reconnect the thermostat tubing to the T port 3b Or reinstall the plug on the CSC 3000 s G port See Step 1b 4 Adjust the thermostat to call for minimum airflow 15 psi or more at T port 5 A...

Page 6: ...pressure gauge to the G port requires 5 32 O D tubing 3 With a small flat blade screwdriver adjust coun terclockwise to increase clockwise to decrease the reset span control at the bottom of the con troller until pressure at the G port equals the desired reset span pressure 3 psig 8 psig 13 psig Thermostat Pressure Max Airflow Min Airflow New Reset Start Point 3 psig Old Reset Start Point 8 psig R...

Page 7: ...stat send an adequate signal to the controller Are LO STAT and HI STAT set correctly for the thermostat action When cycled can the control ler repeat the LO STAT and HI STAT settings If the LO STAT or HI STAT must be set for 0 wc see the notes about zero minimum in DIRECT Reset Minimum and Maximum on page 4 or RE VERSE Reset Minimum and Maximum on page 5 Maintenance No routine maintenance is requi...

Page 8: ... 09 10 15 20 25 30 40 50 80 70 60 1 0 90 CFM Flow Rate as read by sensor Differential Pressure P in Inches w c NOTE This chart is for illustration only Do not use this chart to obtain your values It is NOT intended for calibration of your Minimum and Maximum adjustments This airflow chart is an example of the charts usually affixed to the VAV box Each chart is specific for the type of flow sensor ...

Page 9: ...ressure flow pickup needs to be replace with KMC SSS 1000 series See KMC CSC Cross Reference to Universal CSC 3000 Series chart above All Titus CSC 2000 Series controllers are the same as KMC CSC 2000 Series KMC CSC Cross Reference to Universal CSC 3000 Series Universal Replacement KMC Model Older KMC Model CSC 3011 CSC 1001 CSC 2001 CSC 2003 CSC 2007 CSC 2011 Discontinued CSC 2013 Discontinued CS...

Page 10: ...ide Rev G Applications DA Thermostat NO or NC Damper RA Thermostat NO or NC Damper Cooling These instructions do not apply to the CSC 3014 or the CSC 3501 3505 LO STAT Min Flow HI STAT Max Flow Reset Range 8 to 13 psi LO STAT Max Flow HI STAT Min Flow Reset Range 3 to 8 psi ...

Page 11: ...e DA Thermostat NO or NC Damper and NO Hot Water Valve RA Thermostat NO or NC Damper and NC Hot Water Valve LO STAT Min Flow HI STAT Max Flow Reset Range 8 to 13 psi Hot Water Valve NO Spring Range 3 to 8 psi LO STAT Max Flow HI STAT Min Flow Reset Range 3 to 8 psi Hot Water Valve NC Spring Range 8 to 13 psi ...

Page 12: ...tches Stage 2 On with Decrease Stage 3 Off with Increase Stage 1 On with Decrease Stage 2 Off with Increase Stage 3 On with Decrease Stage 1 Off with Increase LO STAT Max Flow HI STAT Min Flow Reset Range 3 to 8 psi NO PE Switches RA Thermostat NO or NC Damper and NO Heating P E Switch Stage 2 On with Decrease Stage 3 Off with Increase Stage 1 On with Decrease Stage 2 Off with Increase Stage 3 On ...

Page 13: ...Guide Rev G Dual Duct Cold Deck CSC 3011 10 Damper NC LO STAT Min Flow HI STAT Max Flow Reset 8 to 13 psi Hot Deck CSC 3021 10 Damper NO LO STAT Max Flow HI STAT Min Flow Reset 3 to 8 psi Or use a CSC 3011 10 and change the reset from 8 to 3 See Reset Start Point on page 6 ...

Page 14: ...Controllers 14 Applications Guide Rev G Dual Duct Constant Volume Cold Deck Common Discharge CSC 3011 10 Damper NC LO STAT Constant Volume Flow Reset 8 to 13 psi Hot Deck CSC 3011 10 Damper NO LO STAT Min Flow HI STAT Max Flow Reset 13 to 8 psi ...

Page 15: ...ns 3 Cooling 10 Cooling with Heating P E Switch 12 Cooling with Heating Valve 11 Cross References 9 CSC 3011 9 13 14 CSC 3014 2 CSC 3016 9 CSC 3021 9 13 CSC 3025 9 CSC 3026 9 CSC 3501 3505 2 D Damper Action 4 Direct Reset 4 Dual Duct 13 Dual Duct Constant Volume 14 G G Port 4 Index H HI STAT 5 6 Hot Deck 13 14 I Important Notices 7 L LO STAT 4 5 6 M Magnehelic Gauge 8 Maintenance 7 Minimums and Ma...

Reviews: