HPO-9007 Series Gateways Installation Guide 

1 923-019-05B

HPO-9007 Series Gateways

Installation Guide

However, in practice, 

the maximum distance will 

be substantially reduced by obstacles in the 

path, the shape of the room, sources of radio 

interference, and placement/orientation of the 

sensors and gateway!

See the application guide 

Planning for Wireless 

Sensors 

for important information about proper 

placement of sensors and their gateway.

NOTE: 

KMC 

STW-6010

STW-6014

, and 

THW-1102

 wireless sensors require 

optimizing installation locations 

for adequate 

RF range

 to the 

gateway, adequate 

light

 for sensor 

charging, 

AND 

accurate 

temperature

 

measurement. These factors may 

require repositioning the gateway 

from its original intended location to 

optimize RF range to the sensors. 

Testing operation 

before

 permanent 

mounting is recommended. See the 

sensors 

installation guide

 for mor

information.

REMOVE BACKPLATE

1.  Turn the 

hex screw

 

clockwise

 into the 

backplate until the screw clears the cover.

NOTE: 

The hex screw should remain in the 

backplate.

INTRODUCTION

Complete the following steps to:
•  Mount a KMC Conquest™ HPO-9007NW or HPO-

9007DW gateway

•  Connect it to a KMC Conquest BAC-59xx/9xxx 

controller

•  Discover wireless sensors

NOTE: 

The HPO-9007s only receive signals 

from sensors. They do not transmit 

signals to devices.

NOTE: 

See the data sheet at 

kmccontrols.

com

 for specifications and other 

information.

NOTICE

OBSERVE PRECAUTIONS 

FOR HANDLING

ELECTROSTATIC

SENSITIVE DEVICES

SELECT MOUNTING LOCATION

For the RF signal, the maximum theoretical 

straight-line distance between the gateway 

and sensors is about 100 feet (30 meters). 

CONTENTS

Introduction .........................................................1
Select Mounting Location ......................................1
Remove Backplate ................................................1
Connect Ethernet Cable .........................................2
Install Cover ........................................................2

Configure

 ............................................................2

Software and Firmware Requirements ..................2

Convert and Configure the Sensor Object

 .............3

Add Sensors ....................................................3

Configure Value and Programming Objects

 ...........4

Use of HPO-9001 Distribution Module

 ......................5

Troubleshooting ...................................................5
Maintenance ........................................................6
Important Notices .................................................6

KMC Controls, 19476 Industrial Drive, New Paris, IN 46553  

/

  877.444.5622  

/

  Fax: 574.831.5252  

/

  

www.kmccontrols.com

Summary of Contents for Conquest HPO-9007 Series

Page 1: ... into the backplate until the screw clears the cover NOTE The hex screw should remain in the backplate INTRODUCTION Complete the following steps to Mount a KMC Conquest HPO 9007NW or HPO 9007DW gateway Connect it to a KMC Conquest BAC 59xx 9xxx controller Discover wireless sensors NOTE The HPO 9007s only receive signals from sensors They do not transmit signals to devices NOTE See the data sheet a...

Page 2: ...nnect software ver 1 0 13 x or later KMC TotalControl software ver 4 5 0 x or later See the documents or Help systems for the respective KMC tools for more information If the the HPO 9007 is connected to an optional HPO 9001 NetSensor distribution module for use Hex Screw 2 Pull the cover off the backplate CONNECT ETHERNET CABLE 3 Feed the Ethernet patch cable from the Conquest controller through ...

Page 3: ...that is inside of the sensor body Add Sensors Method 1 Automated KMC Sensor Discovery NOTE For devices other than KMC STW THW sensors use Method 2 1 On the back of the sensor press the Learn button on the side or top of the button body dependent on the model with a small screwdriver 2 In Gateway Sensor List Properties wait until the fields for the sensor to populate with an icon and profile NOTE I...

Page 4: ...bject column and select the relevant AV object s in the drop down box es 5 If desired click in the Location column to add a description of the sensor s location 6 Click Save Changes Configure Value and Programming Objects 1 Configure the relevant AVs as needed from the above steps e g add object names and units and click Save Changes NOTE For temperature in degrees C or humidity only you are done ...

Page 5: ...ill be transmitted within a few minutes NOTE Momentarily pressing the Learn button sends a new identification transmission immediately but that transmission does not include sensor temperature setpoint or humidity values USE OF HPO 9001 DISTRIBUTION MODULE To use multiple HPO 9007 gateways and or STE 9000 series NetSensors on a single controller an HPO 9001 distribution module is required The HPO ...

Page 6: ...ith respect to this document In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 e mail info kmccontrols com 2020 KMC Controls Inc Specifications and design subject to change without notice The sensors m...