HPO-9007 Series Gateways Installation Guide
1 923-019-05B
HPO-9007 Series Gateways
Installation Guide
However, in practice,
the maximum distance will
be substantially reduced by obstacles in the
path, the shape of the room, sources of radio
interference, and placement/orientation of the
sensors and gateway!
for important information about proper
placement of sensors and their gateway.
NOTE:
KMC
, and
wireless sensors require
optimizing installation locations
for adequate
RF range
to the
gateway, adequate
light
for sensor
charging,
AND
accurate
temperature
measurement. These factors may
require repositioning the gateway
from its original intended location to
optimize RF range to the sensors.
Testing operation
before
permanent
mounting is recommended. See the
sensors
information.
REMOVE BACKPLATE
1. Turn the
hex screw
clockwise
into the
backplate until the screw clears the cover.
NOTE:
The hex screw should remain in the
backplate.
INTRODUCTION
Complete the following steps to:
• Mount a KMC Conquest™ HPO-9007NW or HPO-
9007DW gateway
• Connect it to a KMC Conquest BAC-59xx/9xxx
controller
• Discover wireless sensors
NOTE:
The HPO-9007s only receive signals
from sensors. They do not transmit
signals to devices.
NOTE:
See the data sheet at
for specifications and other
information.
NOTICE
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
SELECT MOUNTING LOCATION
For the RF signal, the maximum theoretical
straight-line distance between the gateway
and sensors is about 100 feet (30 meters).
CONTENTS
Introduction .........................................................1
Select Mounting Location ......................................1
Remove Backplate ................................................1
Connect Ethernet Cable .........................................2
Install Cover ........................................................2
............................................................2
Software and Firmware Requirements ..................2
Convert and Configure the Sensor Object
Add Sensors ....................................................3
Configure Value and Programming Objects
Use of HPO-9001 Distribution Module
Troubleshooting ...................................................5
Maintenance ........................................................6
Important Notices .................................................6