HPO-9007 Series Gateways Installation Guide
2 923-019-05B
INSTALL COVER
6. Place the cover over the top of the backplate
and swing it down.
NOTE:
Be careful not to pinch the Ethernet
cable.
7. Turn the
hex screw
counter
clockwise until it
engages the cover.
CONFIGURE
Software and Firmware Requirements
The gateway becomes operational after it is
connected to a powered KMC Conquest controller.
Controllers must have
firmware
version R1.4.0.x
or later for full functionality.
Configuration of the gateway and connected
sensors is performed with one of these software
tools:
•
software (ver. 1.0.13.x or later)
•
™
software (ver. 4.5.0.x or later)
See the documents or Help systems for the
respective KMC tools for more information.
If the the HPO-9007 is connected to an optional
HPO-9001 NetSensor distribution module (for use
Hex
Screw
2. Pull the cover off the backplate.
CONNECT ETHERNET CABLE
3. Feed the Ethernet patch cable from the
Conquest controller through the center of the
backplate.
NOTE:
The Ethernet patch cable should be a
maximum of 150 feet (45 meters).
NOTE:
To use multiple gateways and/or
NetSensors on a single controller, see
Use of HPO-9001 Distribution Module
4. Mount the backplate on an electrical box or
non-metal panel using the provided screws.
5. Plug the Ethernet cable into the modular jack
of the gateway.