CMC-1001
1
Installation Guide
Installation Guide
Non-Metallic Positive Positioner
CMC-1001
Mounting
The CMC-1001 mounts directly on MCP-1030/1130/
1040/1140/1160/5140/5160 series actuators.
1. At the mounting location, remove
one
of the
screws or bolts that holds the
actuator
housing
together.
Do NOT remove more than one
actuator screw or bolt.
2. Slide the positioner over the mounting boss.
3. Reinstall the screw or bolt.
Be careful not to
cross-thread the actuator housing.
4. Using the proper hole in the feedback arm (VTD-
1500), slide the arm over the actuator shaft. The
arm is held between the shaft and the damper
linkage.
5. Connect the 5 psi or 10 psi feedback spring
(ordered separately—see chart) to the hole at the
base of the feedback arm.
Mounting 1
Connections 2
Maintenance 2
Adjustments and Calibration 2
More Information 2
Important Notices 2
All dimension are in inches (mm)
6. Connect the other end of the feedback spring
to the feedback chain. There should be no slack
between the positioner and the arm.