Mounting

The CMC-1001 mounts directly on MCP-1030/1130/ 

1040/1140/1160/5140/5160 series actuators.
1.  At the mounting location, remove 

one

 of the 

screws or bolts that holds the 

actuator

 housing 

together. 

Do NOT remove more than one 

actuator screw or bolt.

2.  Slide the positioner over the mounting boss.
3.  Reinstall the screw or bolt. 

Be careful not to 

cross-thread the actuator housing.

4.  Using the proper hole in the feedback arm (VTD-

1500), slide the arm over the actuator shaft. The 

arm is held between the shaft and the damper 

linkage.

5.  Connect the 5 psi or 10 psi feedback spring 

(ordered separately—see chart) to the hole at the 

base of the feedback arm.

Mounting 1
Connections 2
Maintenance 2
Adjustments and Calibration  2
More Information  2
Important Notices  2

All dimension are in inches (mm)

6.  Connect the other end of the feedback spring 

to the feedback chain. There should be no slack 

between the positioner and the arm.