CMC-1001  

Installation Guide

© 2014 KMC Controls, Inc.   

107-019-01B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Important Notices

The material in this document is for information pur-

poses only. 

The contents and the product it describes 

are subject to change without notice.

 KMC Controls, 

Inc. makes no representations or warranties with respect 

to this document. In no event shall KMC Controls, Inc. 

be liable for any damages, direct or incidental, arising 

out of or related to the use of this document.

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliabil-

ity, and performance. Careful installation will also 

ensure long-term reliability and performance.

Adjustments and Calibration

Once connections are complete and supply air is 

applied, turn the start-point adjustment dial until the 

actuator begins to move.
For example, a start point of 4 psi with a 5 psi span 

spring will yield an operating range of 4–9 psi.

Connections

1.  Using 1/4" (6 mm) O.D. FR tubing, connect the 

main air supply to the center 3/16" (5 mm) port. 

Provide a supply of clean, dry, 20–30 psi (38–207 

kPa) control air.

2.  Connect the control signal to Port 2 (input).
3.  Connect Port 1 (output) to the actuator. For 3" and 

4" actuators (only), insert the small beige in-line 

restrictor (VTD-2500) in the line between Port 1 

and the actuator. The restrictor is not needed for 

6" actuators.

More Information

For 

accessories, speci-

fications, and other 

information

, see the 

CMC-1001 Data Sheet 

on the KMC web site 

(

www.kmccontrols.

com

).

 CAUTION

Pneumatic devices must be supplied with clean, dry 
control air. Any other medium (e.g., oil or moisture 
contamination) will cause the device to fail.