Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long-term reliabil-
ity, and performance. Careful installation will also
ensure long-term reliability and performance.
Adjustments and Calibration
Once connections are complete and supply air is
applied, turn the start-point adjustment dial until the
actuator begins to move.
For example, a start point of 4 psi with a 5 psi span
spring will yield an operating range of 4–9 psi.
Connections
1. Using 1/4" (6 mm) O.D. FR tubing, connect the
main air supply to the center 3/16" (5 mm) port.
Provide a supply of clean, dry, 20–30 psi (38–207
kPa) control air.
2. Connect the control signal to Port 2 (input).
3. Connect Port 1 (output) to the actuator. For 3" and
4" actuators (only), insert the small beige in-line
restrictor (VTD-2500) in the line between Port 1
and the actuator. The restrictor is not needed for
6" actuators.
More Information
For
accessories, speci-
fications, and other
information
, see the
on the KMC web site
(
).
CAUTION
Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.