Humidifier interior
(except post-evaporator)
When using cleaning agents, the technical usage instruc-
tions supplied by the manufacturer should be the first point
of reference (see annex). The water used for rinsing should
be of at least drinkable quality.
Cover the air inlets and outlets of the device where
possible (it is important to minimise the amount of spray
cleaner that infiltrates the nearby ducts).
Apply the cleaning agent using a paintbrush, brush
or spray gun (Care should be taken to ensure that the
cleaning chemicals do not come into contact with the
door seals).
Please observe the exposure time specified by the
manufacturer
Repeat the process until the deposits have been re-
moved satisfactorily.
Ensure sufficient neutralisation and rinsing with fresh
water to remove any traces of cleaner and rinse all cor-
ners with a water jet.
Additional rinsing of the drain troughs.
Ensure sufficient ventilation for the air-conditioning
control unit!
Caution!
Residual cleaning agents or disinfectants may cause an
unpleasant odour if they are not sufficiently rinsed away.
It is important to ensure that following the maintenance
operations, all traces of the cleaning agents are eliminated
from the humidifier.
Cleaning of the droplet separator
((Aerosol separator made of stainless steel mesh )
The droplet separator of the high-pressure humidifier also func-
tions as a post-evaporator. It serves to bind excess water and
release it back into the air by evaporation. The droplet separator
is made of 1.4305 stainless steel.
Due to the use of osmosis water, residues on the droplet
separator are only possible due to an unclean air intake. If
contamination occurs, cleaning by means of a water jet up to
max. 20 bar is permissible. Handling must be carried out with
appropriate sensitivity. However, the use of a soft water jet from
the mains is recommended. Cleaning must not be carried out
mechanically with scraping, grinding or abrasive tools and
aids. Cleaning agents with a pH value of 4-7 should be used to
loosen dirt. Cleaning can also be carried out by using hot water
in combination with a suitable cleaning agent.
With regular maintenance, the separators are not subject
to wear and tear and therefore do not need to be replaced
regularly.
Cleaning and disinfection