In case when any defective device function is noticed  (increased noise level, vibrations, redu- 
ced flow efficiency),   disconnect the fan from the power supply, and to undertake its technical 
revision in order to spot the reason of the functional disturbance. 
Most typical disturbances and their reasons are exposed in the Section 8. 
 

8.

 

Trouble Shooting Guide 

Table No.15 

 

Problem 

Possible reason 

Corrective action  

1. 

The fan cannot be  

Fade out of one of the phases 

Supply correct voltage, 

 

switched on 

is observed  or  

check the protection. 

 

 

voltage is too low  or the impeller  Remove the object 

 

 

is blocked. 

blocking he impeller. 

2. 

Sudden vibrations of the 

Obstacle objects reducing the 

Disconnect the fan from the 

 

fan are occurring 

air flow got stack in the fan 

power supply system, 

 

 

 

take off the hood  and  

 

 

 

remove the obstacle 

 

 

The impeller is faulty 

Replace the impeller for new 

3. 

The fan is working too noisy  Improper impeller rotation sense  Change the impeller rotation 

 

or its flow efficiency is too  

 

sense by swapping phase 

 

weak 

 

connection sequence 

 

9.

 

Maintenance 

Construction provides operational longevity,  robustness,  reliable function, under the condition 
of appropriate operational use and correctly executed maintenance. 

To obtain correct

 functional performances and to meet 

the safety rules, it is recommended to sub-

 

mit the fan to technical revisions in regular periods of time  (i.e. once a year).  During the check  
take into account the function of the fan as well as its technical state. 

 

 

 

 All the activities connected with

 technical revisions on the fan have to be 

carried out 

by an authorised person with adequate

 qualifications

 and

 necessarily after dis- 

connection from the power supply system

.

 

To disconnect the fan from the power supply system, use an isolating switch (IS), which 

should

 

be ordered and installed by User. Isolating switch ought

 to be 

installed

 within reach  

of the servicer.

 

IS isolating switches are offered by KLIMAWENT S.A. as additional accessory. The way of con-
nection is shown in the operation manual of the insolating switch (IS). 

There are subsequent activities within the range of technical revision

:

 

●  examine and tighten up the mechanical- and electrical connections, 
●  check the mounting of the motor and fan, mind the clearance between the bent profiles and  

the impeller is equalised in the whole circumference, 

●  remove the impurities (eventually) deposited inside the fan. 

Prior to the re-start of the fan

  carry out the revision steps listed  

in the Section 6  “Assembly 

and Start-

up” of the present Use and Maintenance Manual. 

Exemption from this are tests that

 need 

to be carried out on the

 device being in run, along  

with the strictly followed safety regulation  

–  as an example  –  measuring of vibrations. 

In the course of the revision activities

  

it is important to follow the safety regulations 

– otherwise  

the personnel / User can be at 

risk

.  Construction of the fan

 

guarantees its operational use when

 it 

is submit to proper maintenance. 

 

Summary of Contents for SMART-160/3000-N

Page 1: ...812W70 SMART 400 750 N 31 05 2019 EN 812W61 SMART 200 1000 N 31 05 2019 EN 812W71 SMART 400 1000 N 31 05 2019 EN 812W62 SMART 200 1500 N 31 05 2019 EN 812W72 SMART 400 1500 N 31 05 2019 EN 812W63 SMA...

Page 2: ...of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parliament and of the Council with regard to ecodesign requirements for fans driven by motors with an electric input power...

Page 3: ...ional use 4 Technical Data Table No 1 Type of the fan Synchronous rotations Supply voltage Motor rate Maximum volume flow Maximum fan pressure Weight r p m V Hz kW m h Pa kg SMART 160 3000 N 3000 3 x...

Page 4: ...2019 Flow charts Table No 2 SMART 160 3000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 79 69 62 59 71 Table No 3 SMART 200 1000 N Acoustic pressure level dB A outlet inlet 1 m 5...

Page 5: ...sure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 79 69 62 59 71 Table No 4 SMART 250 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 65 56 48 44 53 SMART 250 1500 N Acoustic p...

Page 6: ...oustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 68 59 51 48 59 SMART 315 1500 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 80 70 63 60 70 SMART 315 3000 N Acoustic p...

Page 7: ...ustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 63 55 46 43 53 SMART 400 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 73 62 56 52 62 SMART 400 1500 N Acoustic pr...

Page 8: ...MART N 31 05 2019 Table No 7 SMART 500 750 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 69 59 52 49 61 SMART 500 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m...

Page 9: ...ROOF FANS SMART N Table No 8 SMART 630 750 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m 1 m 77 67 60 56 70 SMART 630 1000 N Acoustic pressure level dB A outlet inlet 1 m 5 m 10 m 15 m...

Page 10: ...a motor with a radial impeller Impeller is statically and dynamically balanced according to ISO 14694 2003 AMD1 2010 gaining the G 2 5 class Lower skeletons of the 3000 r p m synchronous rotation fans...

Page 11: ...fans of 3000 r p m Fig No 1 Fans of SMART N types structure and dimensions Table No 10 Dimensions of the fans type SMART N except for fans of rotational speed 3000 r p m Type of the fan A B C D E Qua...

Page 12: ...on a roof of the industrial building it is important to install it on a pedestal with a suitable roof base It is recommended to apply the TPD N or TPDC N sound absorbing roof bases delivery on separat...

Page 13: ...and positioned at the place of operation Connection flange Fig No 3 Connection flange of the fan dimensions Table No 12 Dimensions of the connection flanges Type of the fan Connection flange A mm B mm...

Page 14: ...C 160 N 160 430 630 625 SMART 200 N TPDC 200 N 200 430 630 625 SMART 250 N TPDC 250 N 250 530 730 950 SMART 315 N TPDC 315 N 315 530 730 950 SMART 400 N TPDC 400 N 400 790 990 1200 SMART 500 N TPDC 50...

Page 15: ...the fan even for a check before the hood is reinstalled CAUTION 1 Insulation class I 2 Ingress protection IP54 3 Setting of the motor protective switch Q1 It 1 1 x In where In means rated current o th...

Page 16: ...egular periods of time i e once a year During the check take into account the function of the fan as well as its technical state All the activities connected with technical revisions on the fan have t...

Page 17: ...t be neither thrown nor knocked down Do not put any additional load on the device It is inadmissible to put one device on top of another no stacking During the transport protect them from atmospheric...

Page 18: ...s Journal of Laws L 285 of 31 10 2009 327 2011 EU Guideline of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parlia ment and of the Council with regard to ecodesign require...

Page 19: ...19 31 05 2019 RADIAL ROOF FANS SMART N NOTES...

Page 20: ...20 RADIAL ROOF FANS SMART N 31 05 2019 NOTES...

Reviews: