Klimawent 808W18 Use And Maintenance Manual Download Page 8

                                   8 

                                            

chem-proof Ex roof fan

  SPARK-CHEM/Ex                    

 

       04.06.2019 

   

 

 

CAUTION:  Isolating switch ought to be installed beyond the explosion risk area, near the fan. 

 
 

7.  Operational Use 

Construction and reliable execution of the fan provide longevity of operational use without the 
everyday routine technical supervision.  

Periodically,  examine the mechanical and electri- 

cal connections, the state

 of grounding, and additionally provide efficient cooling to the 

motor

.  

During the use check subsequent aspects: 

– 

operational quality of the motor 

– 

occurrence of eventual vibrations 

– 

width of the circumferential clearance between the impeller and the inlet confusor (funnel) 

– 

the state of the fan grounding 

– 

the state of the hood, shielding 

 

Stop the fan in case of: 

– 

excessive vibrations and noise 

– 

motor overheating 

– 

smoke emerging in the motor 

– 

damage of the fan elements 

 

In case

  

when symptoms

  

of incorrect function

  (

increased

  

noise

  

level,

  

vibrations, redu- 

ced vo

lume flow efficiency

)

 of the device

 

are

 noticed,

  

disconnect the fan from the power 

supply system and

 undertake technical revision in order to spot the causes of 

the

 faulty 

function

.  

 

In case of every repair or the spare part replacement 

(

according to ATEX

 

2014/34 Directive

)

 it is 

important to apply 

the

 adequate information on an 

additional plate

 or in the

 enclosed documentation

 

(

a register log 

of

 repair activities, 

etc

.

).

 

This is the duty of User! 

 

A list of most frequent functional malfunctions  and their corrective measures is listed below. 
 

 

8.  Troubleshooting Guide 

Table No.3 

 

Problem 

Possible reason 

Corrective action  

1

.

 

Sudden drop of the inta-  Obstacle objects, pollutants redu- 

Clean the inlet guard. 

 

ke flow efficiency. 

cing the air flow got stuck at the 

 

 

 

inlet guard. 

 

2

.

 

Sudden vibrations of the  Obstacle objects reducing the air 

Disconnect the fan from the power 

 

fan occur. 

flow got stuck in the impeller. 

system, and remove the obstacle. 

 

 

 

 

 

 

Impeller is defective. 

Replace the impeller and the motor 
for new. 

3

.

 

It is not possible to start  Fade of one of the phases or the 

Adjust  to gain the correct supply  

 

the fan. 

voltage is too low. 

voltage. 

 

 

The block of protections got 

Adjust the correct settings of pro- 

 

 

activated. 

tections. 

 

9.  Maintenance 

 

In the aspect of operational use,  the fan construction

  

guarantees  its efficient function without  

continuous everyday technical supervision

. It is recommended to 

perform technical inspections 

in regular terms, to obtain efficient functional performances of the fan

  

and to meet the rules of 

Occupational Health and Safety.  

 

 

Summary of Contents for 808W18

Page 1: ...nction 5 6 Assembly and Start up 6 7 Operational Use 8 8 Troubleshooting Guide 8 9 Maintenance 8 10 Occupational Health and Safety 9 11 Transport and Storage 9 12 Terms of warranty 10 13 Table of resistance of PVC against various substances 11 14 Sample of the Declaration of Conformity 15 808W18 SPARK CHEM 160 1500 Ex 04 06 2019 EN 808W19 SPARK CHEM 200 1500 Ex 04 06 2019 EN 808W20 SPARK CHEM 250 ...

Page 2: ...of the Council of February 26th 2014 on the harmonisation of the laws of Member States relating to equipment and protective systems intended for use in potentially explosive atmospheres Journal of Laws EC L96 of 29 03 2014 Additionally the appliance meets following harmonized standard EN ISO 12100 2012 Safety of machinery Basic concepts general principles for design Risk assessment and risk reduct...

Page 3: ...gory 2 the device is designed for application in areas where explosive atmosphe res are likely to occur gas hazard G c refers the protection from ignition constructional protection b protection by means of controlling the ignition sources Ex mark of the electrical device constructed and tested according to the European Stan dards for work in areas of explosion hazard execution e type of constructi...

Page 4: ...nical Data Table No 1 Type of the fan Synchro nous rotations 1 min Supply voltage V Motor rate kW Maximum volume flow m3 h Maximum vacuum Pa Acoustic pressure level from distance Weight kg 1 m 5 m dB A SPARK CHEM 160 1500 Ex 1500 3 x 400 0 12 670 110 57 48 10 6 SPARK CHEM 200 1500 Ex 1500 3 x 400 0 18 1330 180 59 50 14 2 SPARK CHEM 250 1500 Ex 1500 3 x 400 0 37 2500 280 66 57 18 3 SPARK CHEM 315 1...

Page 5: ...x 315 339 660 622 8 7 5 Structure and Function Structure of the fan is illustrated on Fig No 3 The subsequent constructional elements of the fan except the impeller are of antistatic plastic PE EL The impeller is made of stainless steel therefore it is possible to forward the chemically aggressive and flammable gases and vapours as a mixture with the air In the course of constructing there were se...

Page 6: ...n inlet is protected with perforated plate that no external objects debris would not get into the impeller space On demand we deliver isolating switches safety switches to cut off the power supply during the installing and servicing activities see catalogue card Electrical Accessories 6 Assembly and Start up Prior to installing examine the delivered fan for damages and impurities occurred during t...

Page 7: ... power supply system strictly according to the Connec tion Diagram located in the inner side of the terminal box cover 6 2 Safety inspection before the start up a Examine if all the mechanical connections are performed correctly b Examine the correctness of the electrical connections phases sequence c Check the correctness of the connection of the motor and the fan housing with the PE pro tective ...

Page 8: ...spare part replacement according to ATEX 2014 34 Directive it is important to apply the adequate information on an additional plate or in the enclosed documentation a register log of repair activities etc This is the duty of User A list of most frequent functional malfunctions and their corrective measures is listed below 8 Troubleshooting Guide Table No 3 Problem Possible reason Corrective action...

Page 9: ...e operational use of the fan are admissible after getting acquainted with the contents of the present Use and Maintenance Manual The fan shall not cause any ha zard under the condition it is correctly and firmly installed within the ventilation system or to the supporting structure Any installation activities related to the power supply system have to be carried out strictly ac cording to the encl...

Page 10: ... use which was in contradiction with the purpose of opera tional use and with the present Use and Maintenance Manual any damages being caused during improper transport storage or incorrect maintenance Infringement of the Clause G Section 3 Reservations of Producer of the present Use and Maintenance Manual and especially modifications undertaken by User on one s own or use in contradiction with the...

Page 11: ...ol butyl alcohol 100 o Liquid chlorine 100 Dry gaseous chlorine 100 Potassium chlorate 7 3 o Sodium chlorate aqueous solution 25 Ammonium chloride aqueous solution all Zinc chloride Ethylene chloride 100 Methyl chloride 100 Potassium chloride aqueous solution saturated Sodium chloride domestic salt aqueous solution saturated Sodium chloride aqueous solution 5 Chlorobenzene 100 Cadmium cyanide Copp...

Page 12: ... Acetic acid icy 100 o Acetic acid aqueous solution 50 Oleic acid 100 o Sulphuric acid 3 50 96 o Sulphuric acid 50 10 Hydrochloric acid 35 Stearic acid 100 Oxalic acid saturated Acidic sodium carbonate aqueous solution saturated Acidic sodium sulphate aqueous solution saturated Nail lacquer o Lysol White liquor 12 5 of the active chlorine o Potassium lye 10 50 Potassium permanganate aqueous soluti...

Page 13: ...oda Vapours of tio urea Vapours of aliphatic hydrocarbons Gaseous ozone Automotive fuel normal petrol Automotive fuel petrol super Automotive fuel diesel oil Paraffin 100 Beer Brake fluid Anti freeze fluid di ethylene glycol Sodium hypochlorite aqueous solution 5 Liquid propane 100 Cresol solution Soap solution saturated Mercury 100 Rum 40 Potassium sulphate aqueous solution saturated Sodium sulph...

Page 14: ...sium carbonate aqueous solution saturated Sodium carbonate aqueous solution saturated Water 100 Chlorinated water saturated Aqua regia nitro hydrochloric acid Seawater Sodium hydroxide 50 Sodium hydroxide caustic soda 100 resistant conditionally resistant with the occurrence hazard of tensioning stress cracks 0 conditionally resistant low resistant not resistant ...

Page 15: ... reduction EN 60204 1 2018 12 Safety of machinery Electrical equipment of machines Part 1 Gene ral requirements EN ISO 13857 2010 Safety of machinery Safe distances to prevent hazard zones from be ing reached by upper and lower limbs EN 80079 0 2013 A11 2014 Electrical appliances in areas of gas explosion risk Part 0 General re quirements EN 60079 7 2016 02 Electrical appliances for areas of gas e...

Page 16: ...16 chem proof Ex roof fan SPARK CHEM Ex 04 06 2019 www klimawent com pl NOTES ...

Reviews: