19

(1). Unscrew and remove caps from 2 and 3-way valves.

 (4). Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.

 (6). Open 2-way valve 1/4 turn then close it after 10 seconds. Check tightness of all joints using liquid

soap or an electronic leak detector.

 (7). Turn 2 and 3-way valves stem to fully the valves. Disconnect vacuum pump flexible hose.

 (8). Replace and tighten all valve caps.

 (5). With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop 
        vacuum pump.

(2). Unscrew and remove cap from service valve.
(3). Connect vacuum pump flexible hose to the service valve.

 How to Purge Air Tubes

  Please read this manual before installing and using it.

 Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.

Testing run the air conditioner after finishing installation, and record details of operation.

        Type of fuse used on indoor unit controller for 9K,12K, 

with 

         rating 3.15 A,250V;

        

18K, 24K is 50T  

Type of fuse used on  inverter outdoor unit controller for 7K,9K,12K is 61T with 

         rating 15 A,250V,for 18K, 24K is 65TS with rating 25A,250V.

       The fuse for the whole unit is to be provided by the user  according to the current at maximum power
        input or use other over-current protective device instead.

   

Installation Instructions

       Accessibility to the plug must be guaranteed even after the installation of the appliance to disconnect
       it in case of need. If not possible, connect appliance to a double-pole switching device with contact 
       separation of at least 1/8 in placed in an accessible position even after installation.

NOTE

NOTE

Test Running

 

Connect to the power source, check if the function selection keys on the remote controller are working

properly.
Check if the room temperature adjustments and timer settings are working properly.
Check if the drain is smooth.
Check if there is any abnormal noise or vibration during operation.
Check if there is leakage of refrigerant.

 

ATTENTION:

If there is no power plug along with the air conditioner,The power cord should be connected to an air
switch ,whose current carrying capacity should be more than 20A and the minimum open-circuit 
distance among the live polar pole,the neutral polar pole and the ground polar pole should be more
 than 3mm.If any malfuctions,please cut off the supply by the air switch and contact the manufacturer 
or its service agent.
The appliance shall be installed in accordance with national wiring regulations.
If the supply cord is damaged. It is better to be replaced by the manufacturer or its service agent or a
similarly qualified person in order to avoid a hazard.

The security out static air pressure for our products is 0.8-1.05 * standard pressure.

Please make replacing with the special assembly purchasing from our factory or our 
service center if something wrong with Interconnection cable.

The biggest length for our connection pipe can be 49 ft. More 20 g refrigerant is
 necessary for per miter if the length is over 23 ft. The biggest diversity for altitude
 between indoor and outdoor unit is 16 ft.

 Please do not place valuable things under the unit after installation. 

Summary of Contents for SPLIT AIR-CONDITIONER

Page 1: ...ome this Owner s Manual should be read carefully be fore using your air conditioner Afterre ading st ore it in a safe place P lease refer to the manual for questions on useo rin the event that any irr...

Page 2: ...s any button when the flashes If you dont press any button within 10 seconds the remote controller is pre set as Heat Pump automatically the symbol will flash from Cool and HEAT alternatively heating...

Page 3: ...us injury etc SLEEP FAN TIMER SWING ON OFF MODE MED LO SWING AUTO HI DRY FAN HEAT COOL FEEL SLEEP TIMER ON OFF Use correct power supply in accordance with the rating plate requirement Otherwise seriou...

Page 4: ...ntake Air Intake Air Outlet Louver Vertical Adjustment Louver Horizontal Adjustment Electrostatic Filter optional Charcoal Filter optional Air Filter Remote Controller Front Panel Emergency Panel Disp...

Page 5: ...t when the remote controller is out of work If there is any difference between the sketch map and the substantiality please subject to the substantiality R unIndic ator It is on during operation S lee...

Page 6: ...ortable SLEEP Used to start and stop operation Used to adjust airflow direction Used to select TIMER operation Signal Transmitting Window Transmits signals to the system Setting Display Transmitting d...

Page 7: ...or each time the batteries are replaced as they are discharged the remote control mades a short Auto Test all the symbols can be displayed are shown on the screen and keep 2 seconds then the symbol wi...

Page 8: ...m air conditioner aim the remote control to the signal receptor The remote control will operate the air conditioner at a distance of up to 23 ft when pointing at signal receptor of indoor unit Remote...

Page 9: ...possible with the button or the button Press the MODE select button Move the MODE to the FEEL position 1 2 Operates by selecting automatically the operation mode HEAT DRY FAN COOL depending on the ro...

Page 10: ...nds SLEEP operation is switched from Normal SLEEP to SLEEP alternatively Comfortable Used to set or cancel sleep operation This function is invalid in fan and dehumidify mode This function is invalid...

Page 11: ...usty environment Stop the appliance and remove the air filter 1 Open the front panel 2 Press the handle of the filter gently from the front 3 Grasp the handle and slide out the filter soft cloth to cl...

Page 12: ...5 minutes later In HEATING operation the appliance will defrost de ice automatically to raise efficiency This procedure usually lasts 2 10 minutes During defrosting fans stop operation After defrostin...

Page 13: ...e power supply and connect back 2 3 seconds later Changing mode during operation 3 minutes will delay This odor may come from another source such as furniture cigarette etc which is sucked in the unit...

Page 14: ...hould be over 6 in should be over 79 in should be over 12 in Installation must be performed in accordance with the national wiring standards by authorized personnel only Above figure is only a simple...

Page 15: ...re is no obstacle near the air outlet and air can be easily blown to every corner Where piping and wall hole can be easily arranged Keep the required space from the unit to the ceiling and wall accord...

Page 16: ...a sleeve through the wall hole to keep the wall tidy and clean Drill a hole on the wall The hole should tilt a little downward toward outside Decide the position of hole for piping according to the 2...

Page 17: ...lation tube Power cord 1 for heat pump Power cord Defrost cable for heat pump Drain hose prepared by user A Insert the pipe fixer to the slot B Press to hook the pipe fixer onto the base Base Base Bas...

Page 18: ...ble thickness is as specified in the power source specification See the cable specification table below 3 Check the wires and make sure that they are all tightly fastened after cable connection 4 Be s...

Page 19: ...ct the condensate water Just install the drain port and rubber washer to the chassis of the outdoor unit then connect a drain hose to the port as the right figure shown The air which contains moisture...

Page 20: ...tdoor unit Connetting indoor unit Connetting power Indoor Unit 3 N 1 2 L Connetting outdoor unit Indoor Unit N 1 L Outdoor Unit N 1 L N L Outdoor Unit 3 N 1 2 L N L 1 N 1 2 3N Cooling Heating 12 3N Co...

Page 21: ...o a double pole switching device with contact separation of at least 1 8 in placed in an accessible position even after installation NOTE NOTE Test Running Connect to the power source check if the fun...

Page 22: ...5 594 4972 Fax 305 675 2212 www klimaire com sales klimaire com 2190 NW 89 Place Doral FL 33172 USA The Klimaire logo is a registered Trademark of Klimaire Products inc Copyright 2010 Klimaire Product...

Reviews: