50
4
Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
SECTION 3 MENUS
Assume that for analog output 1, output connection was selected as 4-20 mA (refer to
). Then, operator should adjust the “analog output 1” dip switch as seen in
(Vout1 -> OFF; Iout1 -> ON). After the dip switch adjustment, setting will be completed.
OFF
ON
IO
ut4
VO
ut4
IO
ut3
VO
ut3
IO
ut2
VO
ut2
IO
ut1
VO
ut1
Fig. 3-42 Vout1 -> OFF; Iout1 -> ON
In order to obtain voltage output, Vout1 should be set to ON, and Iout1 should be
set to OFF. If both switches are ON or OFF at the same time, analog output will not
operate correctly.
In order to obtain current output, Vout1 should be set to OFF, and Iout1 should be set
to ON. If both switches are ON or OFF at the same time, analog output will not operate
correctly.
If the setting of output connection and setting of the dip switch are incompatible,
related analog output will not operate correctly.
3.2.1.1.6.1.3 Min. value
The minimum value for the selected input mode.
Refer to 3.2.1.1.6.1.5 Multiplier setting.
3.2.1.1.6.1.4 Max. value
The maximum value for the selected input mode
Refer to 3.2.1.1.6.1.5 Multiplier setting.
If “Min. value” and “Max. value” are adjusted to be the same, then analog output will
not operate.
3.2.1.1.6.1.5 Multiplier
When ‘Multiplier’ is selected, press OK key and the options in
will appear on the
screen. Press up and down keys to select the desired option and press OK key to complete
the setting. Multiplier coefficie t options are as follows:
• 1
• Kilo (1000)
• Mega (1000000)
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...