SECTION 3 MENUS
3.2.1.1.4.1.2 Delay
Digital input delay can be adjusted between 10 2000 milliseconds.
In order for ‘2nd tar
iff
’ or ‘Counter’ modes to be activated; DI1 and GND pins should be
short-circuited at least “delay” period of time. (for Virtual Keyboard
.
Delay 100 msec
Fig. 3-32
Delay
E.g.:
Digital input : Input1
Mode
: Counter,
Delay
: 200 msec
When DI1 and GND pins are short-circuited for minimum 200 msec, ‘Input 1 Counter’
increments by 1.
E.g.:
Digital input : Input1
Mode
: Tariff
Delay
: 200 msec
In order for the Tariff 2 meter to be active, DI1 and GND pins should be short-circuited for
minimum 200 msec. Tariff 2 me er will be active during the course of short circuit time.
tariff 1 counts
DI1 and GND
short circuit
<200msec>
DI1 and GND
short circuit
<100msec>
DI1 ve GND
open circuit
Time
Tariff 1 counts
tariff 2 counts
Fig. 3-33
Tariff 1 or Tariff 2 ctivation
3.2.1.1.4.2 Input 2 Menu
Input 2 applications and settings are the same as Input1. Digital input2 operates with DI2
and GND pins.
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...