As previously stated in the installations sheet, the Intrinsically Safe Sounder 

Range 

must

 be powered via a suitable Zener Barrier or Galvanic Isolator whose 

characteristics do not exceed:

Uo:28v, Io: 93mA, Po:660mW

The value for Uo must be between 

16v and 28v

, and Io should not be below 

50mA. 

This range of products is only to be powered via a correctly rated Zener Barrier 

or Galvanic Isolator.  To power these units up without the correctly rated barrier 

could damage these products and so void any protection ratings.

Specific Conditions of Use:

1. Clean equipment regularly to prevent dust build-up with a damp or anti- 

  static cloth only.

2. Equipment only suitable for fixed installation.

3. It must be ensured that the equipment is installed in accordance with   

  IEC 60079-14 and IEC 60079-25 and that capacitance and inductance limits  

  are not exceeded by distributed capacitance (Cc) or distributed inductance  

  (Ic) due to cable length.

Table of Entity Parameters

Parameter

Barrier Supply

Ui

28V

li

93 mA

Pi

660 mW

Li

0

Ci

0

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for TCC-0001

Page 1: ...L INFORMATION PLEASE READ PRIOR TO INSTALLATION Klaxon Intrinsically Safe Sounder Range S00608KL Issue 6 12 10 2018 AUDIBLE SIGNALLING DEVICES APPROVALS AND CONFORMITIES www acornfiresecurity com www...

Page 2: ...ible 2 0 Intrinsically Safe Labelling The product will have an individual serial number printed onto the head base plate an example of the sounder label is shown below These products have been tested...

Page 3: ...ur and if it does it will only exist for a short time Zone 20 Explosive dust air mixture is continuously present Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosiv...

Page 4: ...side cutters or a similar tool To open a locked head remove the small rubber bung from the hole on the side of the sounder insert a tool into the hole and depress the clip whilst twisting the head An...

Page 5: ...lockwise until it comes free Remove the appropriate fixing hole and conduit knockouts from the back box The back box provides IP66 protection For this to be maintained suitably rated minimum IP66 M20...

Page 6: ...nder head unit onto the installed base the alarm tone must be set see page 5 To control the Sounder use either a switch in the safe area on either the positive or negative lines into the Barrier or by...

Page 7: ...pin to 0v as detailed in the table on page 5 For this application a barrier with 2 Diode return paths is required as shown in the diagram below Switching between return paths for the 2 stage system wi...

Page 8: ...section of the installation sheet The Sounder can be turned on and off either by using a suitably placed switch in the positive or negative rails switch must be of suitable ratings if installed in th...

Page 9: ...ity monitoring to take place and a fire panel compatible with Intrinsically Safe products must also be used If required an external switch can be wired in series with the 1 and or 2 connections to giv...

Page 10: ...mal operation The enclosure is non conducting and may generate an ignition capable level of electrostatic charge under certain extreme conditions It is the responsibility of the user to ensure that th...

Page 11: ...rectly rated barrier could damage these products and so void any protection ratings Specific Conditions of Use 1 Clean equipment regularly to prevent dust build up with a damp or anti static cloth onl...

Page 12: ...15 550Hz 0 7s 1000Hz 0 33s O I I I O O 1 93 16 1500Hz 2700Hz 3Hz O I I I I O 1 98 17 750Hz I O O O O O 1 93 18 2400Hz I O O O I O 1 105 19 660Hz I O O I O O 18 93 20 660Hz 1 8s ON 1 8s OFF I O O I I...

Reviews: