25 / 48
83000902.Ka
No.
No.
No.
No.
Parameter
Parameter
Parameter
Parameter
Min. value
Min. value
Min. value
Min. value Max. value
Max. value
Max. value
Max. value Factory
Factory
Factory
Factory setting
setting
setting
setting
Setting
Setting
Setting
Setting
Explanation
Explanation
Explanation
Explanation
13
Control mode
Ct
Ft
Ft
Ct: Combined control
Ft: Fixed value control
14
Heater
function
antifreeze
(optional)
OFF
ON
OFF
Optional if a heater is installed.
ON: +2°C
OFF: +5°C
15
Hot gas bypass (optional)
OFF
ON
OFF
OFF: Bypass control unused
ON: Bypass control activated
When P15 is activated, the switching
hysteresis (P2 and P6) is deactivated.
The PID controller will automatically
aim for optimum switching hysteresis.
This is dependent on the PID setting.
The P, I and D values, cycle time and
switching hysteresis of the controller
are each set in turn.
Range (default):
Proportional band P
0.1 .. 99.9 K (1.0)
Integral time (reset time) I
1 .. 999 sec, 0=inactive (300)
Derivative time D
1 .. 999 sec, 0=inactive (50)
Cycle time C
4 .. 100 sec (10)
Note
Analyse to optimise the controlled
system and contact customer service.
16
Set
point
for
filter
mat
monitoring
4.0 K
70.0 K
(+ OFF)
OFF
Make the setting as follows (setting
range 4.0 .. 70.0 K, switching differ-
ence 2.0 K, fixed setting): Activate the
cooling unit with a clean filter mat
inserted.
Using the keys
and
set the
value approx. 10.0 Kelvin above the
difference between temperature probe
B3 and B4.
17
Changeover °C/°F
°C
°F
°C
°C: Show temperatures in Celsius
°F: Show temperatures in Fahrenheit
18
Evaluation of the external
enable signal
1
5
(+ OFF)
OFF
OFF: Normal operation
1: Standby with signal absent
2: Cooling off with signal absent
3: Control via external controller
4: If signal is present at ext. input, the
clock function is deactivated
5: Standby with signal absent. If the
system is on standby, the alarm re-
lay 1 (contact 4-5) opens