23 / 48
83000902.Ka
7.4
7.4
7.4
7.4
Meaning of the control parameters
Meaning of the control parameters
Meaning of the control parameters
Meaning of the control parameters
No.
No.
No.
No.
Parameter
Parameter
Parameter
Parameter
Min. value
Min. value
Min. value
Min. value Max. value
Max. value
Max. value
Max. value Factory
Factory
Factory
Factory setting
setting
setting
setting
Setting
Setting
Setting
Setting
Explanation
Explanation
Explanation
Explanation
Fixed value control
Fixed value control
Fixed value control
Fixed value control
1
Set
point
temperature
with fixed value control
10.0°C
30.0°C
20.0°C
If fixed value control is set for parame-
ter 13, the set point temperature can
be selected here.
2
Switching hysteresis
with fixed value control
2 K
5 K
2 K
If fixed value control is set for parame-
ter 13, the switching hysteresis can be
determined here.
Combined control
Combined control
Combined control
Combined control
3
Difference from room tem-
perature
-10.0°C
10.0°C
5.0°C
If combined control is set for parame-
ter 13, the set point temperature can
be set with this parameter as the
difference compared to room tempera-
ture. Negative values result in a set
point above the ambient temperature.
4
Minimum set point
7.0°C
P5
10.0°C
If combined control is set for parame-
ter 13, the lower set point can be
limited with this value.
5
Maximum set point
P4
35.0°C
28.0°C
If combined control is set for parame-
ter 13, the upper set point can be
limited with this value.
6
Switching hysteresis,
combined control
2 K
5 K
2 K
If combined control is set for parame-
ter 13, the switching hysteresis can be
determined here.
7
Tolerance for error message
"F.01"
3.0°C
15.0°C
5.0°C
If the cooling medium temperature
exceeds the activation temperature of
the compressor by the value set here,
error message F.01 and an alarm are
generated.
8
Heater control
(Medium)
1.0°C
5.0°C
(+ OFF)
OFF
Optional:
Optional:
Optional:
Optional: If a tank heater is installed.
The heater will cut in if the tank tem-
perature drops below the value set
here.
If OFF is set, the heater will never cut
in.
9
Internal real-time clock
-
-
-
One after another, the hour (0 .. 24),
minute (0 .. 59), year (00 .. 99), month
(1 .. 12), day (1 .. 31), summertime
(OFF, EU; USA, S1 .. S12, E1 .. E12)
are displayed.
10
Switching times
Compressor
OFF
ON
OFF
Select the day of the week (1Mo ..
7Su, ESC), start time (hh, mm), end
time (hh, mm)
11
Switching times
Heater
OFF
ON
OFF
Only if P8 not OFF.
Select the day of the week (1Mo ..
7Su, ESC), start time (hh, mm), end
time (hh, mm)
12
Lock "1"
1
999
123
To call up parameters P13 .. P19, key