Method of boiler cleaning & Maintenance – Error code
kituami
Page 40
○ Breakdown : If water temp. sensor or overheat temp sensor is down.
No.
Trouble type
Actions
04
1. Water temp.
sensor is down.
① Check if the water temp. sensor is connected properly.
② Check if wiring is damaged.
③ Replace the temp. sensor.
05
1. Overheat sensor
is down.
① Check if the overheat sensor is connected properly.
② Check if wiring is damaged.
③ Replace the temp. sensor.
○ Breakdown : If transmission and reception are bad
No.
Trouble type
Actions
06
1. Rotation number
of the blower
is not detected.
① Check if the blower wiring is damaged.
② Replace the blower.
06
1. Row limit
High limit
① If a funnel is installed in wind pressure zone and it is extremely
windy, rotation number of the blower would become high. If it
happened frequently, call the operator for correcting funnel
position.
② If dewfall appeared on the funnel bent, remove condensate.
③ Call local store or A/S center for taking measures.
※ If foreign materials are caught on the blower case,
rotation number of the blower becomes high or low.
08
1. Bad transmission
/reception
① If bad transmission/reception between room control and
main control, : Turn Ignition stroke OFF.
② If it lasts 10 min. or more, "Error 08" would happen and power
would turn on and off.
③ Replace the room control or the main control.