background image

7

Direct wire method: Copper or Aluminum wire

Use this method only if local codes
permit connecting ground conductor to
neutral supply wire.

10. Loosen (do not remove) the 3 slotted

set screws. Insert the neutral (white)
wire into the hole at the bottom of the
center position lug (attached to center
terminal screw of terminal block). See
Figure 3. 

11. Connect the other two wires (lines 1

and 2) to the outer aluminum lugs. 

12. Securely tighten the set screws. 

For 8 gauge copper wire, tighten to 
25 in/lbs of torque, and for 6 gauge
aluminum wire, tighten to 35 in/lbs of
torque to make a proper electrical
connection. See Figure 3.

13. Tighten the locking ring of the conduit

connector. 

14. Replace the terminal block cover.

Use this method for new installations,
mobile homes, recreational vehicles and
whenever four-wire installation is
required.

10. Remove the ground-link screw from

the range frame. Save the ground-link
screw and cup washer. Bend up the
ground link so that it does not contact
the range. See Figures 1 and 2.

11. Connect the green ground wire to the

range using the ground-link screw
and cup washer. The ground wire
must be attached first and must not
contact any other terminal. See 
Figure 2.

12. Loosen (do not remove) the 3 slotted

set screws. Insert the neutral (white)
wire into the hole at the bottom of
the center position lug (attached to
center terminal screw black terminal
block). See Figure 2. 

13. Connect the other two wires (lines 1

and 2) to the outer aluminum lugs. 

14. Securely tighten the set screws. 

For 8 gauge copper wire, tighten to
25 in/lbs of torque, and for 6 gauge
aluminum wire, tighten to 35 in/lbs of
torque to make a proper electrical
connection. See Figure 2.

15. Tighten the locking ring of the

conduit connector. 

16. Replace the terminal block cover.

NOTE:

The bag containing three

aluminum terminal lugs must be used
when making a direct wire connection.

Electrical Shock Hazard

Disconnect power before servicing.

Use 8 gauge copper wire, or 6 gauge
aluminum wire.

Electrically ground range.

Failure to follow these instructions can
result in death, fire, or electrical shock.

WARNING

7.

IMPORTANT:

the aluminum terminal

lugs must be assembled to the
terminal posts with the set screws
facing out as shown.

8.

Attach three aluminum terminal lugs
to terminal posts.

Use a 3/8" nut driver and tighten the
nuts securely. Nuts must be
tightened to 20 in/lbs of torque for
proper electrical connection.

9.

Complete electrical connection
according to your type electrical
supply (“Four-wire electrical
connection” or “Three-wire electrical
connection.”)

This range may be connected directly to
the fuse disconnect or circuit breaker box;
or with a U.L.-listed, 40 amp range power
supply cable. Depending on your
electrical supply, make the required 
three-wire or four-wire connection.

1.

Disconnect power.

2.

Remove the knockout as needed for
conduit connection.

3.

Assemble a
U.L.-listed
conduit
connector in
opening.

U.L.-listed
conduit
connector

4.

Strip outer covering back 3 inches to
expose wires. Strip the insulation back
1 inch from the end of each wire.

5.

Allow enough slack in the wire to
easily attach the wiring terminal
block.

6.

Use 3/8" nut driver and remove the
outside nuts on the terminal block
screws. Do not loosen the factory-
tightened nuts behind the outside
nuts.

3"

1"

Figure 3

ground
link

Figure 1

Figure 2

ground
screw

aluminum
lug

terminal
screw

set screw
must face out

slotted
set screw

green
ground
wire

line 1

line 2

neutral
(center wire)

slotted
set screw

line 1

line 2

neutral
(center wire)

Three-wire electrical
connection:

Four-wire electrical connection:

Summary of Contents for 9.76E+13

Page 1: ...ge is moved Failure to follow these instructions can result in death or serious burns to children and adults 10 10 10 HOME APPLIANCES www kitchenaid com Installation Instructions IMPORTANT Installer Leave Installation Instructions with the homeowner Homeowner Keep Installation Instructions for future reference Read and save these instructions for local electrical inspector s use Write down the mod...

Page 2: ...g codes and ordinances Failure to meet codes and ordinances could lead to fire or electrical shock Proper installation is your responsibility A qualified technician must install this range Make sure you have everything necessary for correct installation It is the installer s responsibility to comply with installation clearances specified on the model serial rating plate The model serial rating pla...

Page 3: ... floor 3 Product dimensions Cabinet dimensions requirements 30 76 2 cm width 24 1 2 62 2 cm 26 3 8 67 cm depth with handle 36 91 4 cm cooktop height 46 13 16 119 0 cm overall height Cabinet opening dimensions shown are for 25 63 5 cm countertop depth 24 61 0 cm base cabinet depth 36 91 4 cm countertop height NOTE 24 61 cm min when bottom of wood or metal cabinet is protected by not less than 1 4 6...

Page 4: ...orage drawer panel A four wire or three wire single phase 120 240 volt 60 Hz AC only electrical supply or three wire or four wire 120 208 volt if specified on the model serial rating plate is required on a separate 40 amp circuit fused on both sides of the line A time delay fuse or circuit breaker is recommended Copies of the standards listed may be obtained from National Fire Protection Associati...

Page 5: ...minum wire depending on the connection needed terminal block cover knockout opening for 40 amp power supply cord knockout opening for power supply cable 8 Remove the terminal block cover located on the back of range Contact a qualified floor covering installer for the best procedure for drilling mounting holes through your type floor covering 7 Use the anti tip bracket template to install the anti...

Page 6: ...crews Do not loosen the factory tightened nuts behind the outside nuts 10 Connect the neutral wire center wire to the center terminal screw on the terminal block See Figure 2 11 Connect the other two wires lines 1 and 2 to the outer screws on the terminal block See Figure 2 12 Securely tighten nuts with 3 8 nut driver for proper electrical connection 13 Tighten the strain relief screws 14 Replace ...

Page 7: ...ighten the locking ring of the conduit connector 16 Replace the terminal block cover NOTE The bag containing three aluminum terminal lugs must be used when making a direct wire connection Electrical Shock Hazard Disconnect power before servicing Use 8 gauge copper wire or 6 gauge aluminum wire Electrically ground range Failure to follow these instructions can result in death fire or electrical sho...

Page 8: ...tion section 14 Place rack in oven Place level on rack first side to side then front to back anti tip bracket range foot 12 Make sure the anti tip bracket is installed Look for the anti tip bracket securely attached to floor Slide range back so rear range foot is under anti tip bracket If range is not level pull range forward until rear leveling leg is removed from the anti tip bracket Use 3 8 dri...

Page 9: ...t and Oven Cavity symbols will light up in the display Press the START ENTER button The bottom element should glow red and the indicator light should be on The upper element should become hot but not glow red The oven indicator light goes off when the oven is preheated Press CANCEL OFF button 19 Check the operation of the broil element Press the BROIL button 500 will appear in the temperature disp...

Page 10: ... Pages of your telephone directory under Appliances Household Major Service Repair You can also obtain the service company s name and number by dialing free within the continental United States the KitchenAid Customer Interaction Center telephone number 1 800 422 1230 A special operator will tell you the name of your nearest KitchenAid authorized service company Maintain the quality built into you...

Page 11: ...11 Notes ...

Page 12: ...12 Part No 9758644 2004 KitchenAid Printed in U S A RegisteredTrademark of KitchenAid Prepared by KitchenAid Benton Harbor Michigan 49022 01 2004 HOME APPLIANCES ...

Reviews: