12
ENGLISH
INSTALLING THE WATER CIRCUIT
Check local regulations
KE 90 H can be installed to circuits with open expansion
vessels (check local regulations), so long as you hook
up the fittings to the coil’s thermal discharge valve..
INSTALLATION
Never light the fire in the hearth (even to test
it) when the circuit is dry (no water); doing so
can irreparably damage the appliance.
PLUMBING
Plumbing depends on the type of system.
However, there are some “general rules”:
•
the presence of an accumulator (tank) is
recommended but not mandatory. Its advantage is
that it releases the boiler from “sudden” requests
from the system and can be integrated with
other heat sources. It reduces fuel consumption
andincreases the efficiency of the system.
•
the return temperature of the water to the
boiler must be higher than 50-55° C to prevent
condensation.. Edilkamin recommends using the
Anti-condensation kit for this purpose
•
An accumulator (tank) is needed to heat
lowtemperature radiant panels, to be installed as
recommended by the manufacturer of the panels
themselves.
•
the material used in the circuit must be suitable to
withstand overheating.
•
direct plumbing to radiators prevents proper
operation, owing to the small diameter of theipipes.
Fit a bleed cock to the boiler's delivery bend.
7,5
14,5
12
13
TERMOPRODOTT
O
2
1
3
4
IMPIAN
TO
Thermo
Product
Storage
tank
The Anti-Condensation Kit does NOT contain the circulator and the safety devices which must be
positioned on the rim of the thermo product or on the system, according to installation standards
in the country.