3
ALARM TABLE
1
LF1
Evaporator temperature sensor failure. In this case all functions and relays are automatically deactivated.
2
LF2
Ice bucket temperature sensor failure where the cycle continues without any interruption
3
ΑLo
Low evaporator temperature alarm
4
ΑHi
High evaporator temperature alarm
5
FFF
Cooling failure. All functions and relays are deactivated automatically after the end of time t3.
The alarm is automatically deactivated by restarting the device.
6
EEE
Upon completion of the defrosting procedure, the evaporator temperature remains less than the SPo. All functions and relays are deactivated automatically.
The alarm is automatically deactivated by restarting the device.
7
FUL
The bucket is full with ice. The ice production stops until the bucket sensor reaches SP2+dF2 temperature.
8
EEr
Error in RAM memory: rewrite the first parameter SP2 (check page 1 – adjusting the Set Point)
The alarms LF1, LF2, ALo, AHi are deactivated automatically when the cause of their activation is no longer present