ICE MACHINE TEMPERATURE CONTROLLER Model ICE  V3  

 

ATTENTION

                                                                                                                                                                                                                                       

Firmware V3

 

 Read carefully these instructions before installing and using this device and keep them for future reference. Attention to installation and electrical wiring. Use this 
device only as described in this document and never use itself as a security device. The device must be disposed of in accordance with local standards for the collection 
of electrical and electronic equipment.  

DESCRIPTION 

ICE

 is an ideal thermostat for sprinkling ice machine. It has two NTC/PTC sensors: one is for the evaporator temperature and the other is for the ice bucket in order to terminate 

the production when the bucket is full. It has 3 indication digits of temperature display with an accuracy of 0.5°C and 4 buttons. Three relays (for compressor 30Α, water pump 
10Α, and defrost 10Α) with NO contact, three adjustable timers in minutes for the control of the compressor/water pump and defrost relays, electrical or HOT-GAS defrost 
mode, OFF mode for the device and an alarm buzzer for high or low temperature. The device is mounted on a panel hole 29x71mm and it is restrained with plastic side brackets. 

  

 

 

 

 

 

 

 

 

 

 

For more indications regarding the alarms please see the alarm’s table at page 3. 
 

DEVICE OPERATION WITH ELECTRIC DEFROST 

 

During start-up, the defrost relay 

 is activated and timer t2 starts counting. The screen displays t2 time duration, which counts backwards, while the indications  

  and

  turn on. If 

the evaporator temperature is lower than the set point after the defrost

, all operations and relays will be deactivated automatically and the screen will 

display the indication “

ΕΕΕ

”. The alarm is automatically deactivated after the restart of the device using the ON/OFF button or by toggling the power supply. 

Manual defrost 

duration is based on timer t2 and does not end based on the defrost end temperature – parameter dE5. 

 

When timer t2 elapses, the defrost relay is deactivated 

 and timer t3 starts counting while the compressor 

 and water pump 

 relays are activated. The display 

shows the current evaporator temperature and the indications 

,

 

T2

 

and 

 light up. When the evaporator temperature reaches the set point, timer 

t1

 begins counting, 

while the compressor and water pump relay remain activated until timer 

t1

 elapses. The display shows time duration of timer 

t1

, which counts backwards, while the indications 

 , 

  and 

 light up. When timer 

t1

 elapses, the compressor and water pump relays are deactivated, and afterwards the cycle starts again with the activation of defrost 

relay, etc. 
 

 

If a malfunction occurs in the cooling circuit and the 

evaporator temperature does not decrease

, the aforesaid process will end based on timer 

t3

. All functions and relays 

will be deactivated automatically and alarm "

FFF

" will be displayed. The alarm is automatically OFF by restarting the thermostat from the power supply or the ON / OFF 

button. 

 

 

When the ice bucket temperature sensor reaches the SP2, the production will stop when the last production of ice drops on the bucket and the cycle ends. On screen the 
indication “

FUL

” is displayed until the bucket temperature reaches SP2+dF2 and the cycle resumes.  

 
The aforesaid cycle repeats continuously without interruption during the smooth operation of the thermostat. 
 
In case 

of evaporator’s temperature sensor failure

 

or OFF device state

, all thermostat functions are deactivated. 

 
In case 

of bucket temperature sensor failure

, the cycle continues and does not stop because of this failure.  

 

HOT-GAS OPERATION

 

Parameter 

do

 set the defrost function in electric or HOT-GAS mode. Only in hot-gas defrost mode (do = 1), the compressor relay works in parallel with the defrost relay, for 

time t2. 
 

1.

 

Press  

 and parameter 

SP2 

is displayed. 

2.

 

Press 

 and its value is displayed while the arrows  

 

 

  change its value. 

3.

 

Press  

  to store the new value. Now the device is operating with the new value. 

 

 

By pressing at the same time  

 and 

 , the device switches ON/OFF. 

INDICATIONS AND BUTTONS FUNCTION 

Display indications 

 

compressor ΟΝ 

 

water pump ΟΝ 

 

defrost ON 

dFr

 

manual defrost ΟΝ 

 

timer ΟΝ 

Τ2 

evaporator temperature 

ΤS 

ice bucket temperature 

 

alarm ΟΝ 

 

malfunction ON 

   Keyboard 

 

enter/exit the parameter’s menu 

 

display the parameter’s value 
enter parameter’s value 

manual defrost  

 

up arrow 
display evaporator temperature 

 

down arrow 
mute buzzer 
ON/OFF device (check below) 
display ice bucket temperature  

ADJUSTING THE ICE BUCKET SET POINT 

 

SWITCHING ON / OFF THE DEVICE 