background image

Parameter’s table 

 

  No 

Parameters description 

         min 

     max 

     default  UOM 

Code 

Entry code in parameters menu = “22” 

 0 

254 

  0 

 

SP1H 

Set Point High in Channel 1 

-99 

2000 

100    °C/mA 

SP1L 

Set Point Low in Channel 1 

-99 

2000 

  0 

  °C/mA 

… 

… 

… 

… 

… 

   

  °C/mA 

16 

SP8H 

Set Point High in Channel 8 

-99 

2000 

100    °C/mA 

17 

SP8L 

Set Point Low in Channel 8 

-99 

2000 

  0 

  °C/mA 

18 

IN1L 

4 mA in Channel 1 corresponds to an indication on screen (see Specification 1) 

-99 

2000 

  0 

 

19 

IN1H 

20 mA in Channel 1 corresponds to an indication on screen (see Specification 1) 

-99 

2000 

2000 

 

… 

… 

… 

… 

… 

 

 

32 

IN8L 

4 mA in Channel 8 corresponds to an indication on screen (see Specification 1) 

-99 

2000 

  0 

 

33 

IN8H 

20 mA in Channel 8 corresponds to an indication on screen (see Specification 1) 

-99 

2000 

2000 

 

34 

Tisc 

Time for automated refreshing of temperature indications on screen   

150 

  6 

sec 

35 

DF1H 

Set Point High differential in Channel 1 

150 

  2 

 

36 

DF1L 

Set Point Low differential in Channel 1 

150 

  2 

 

… 

… 

… 

… 

… 

   

 

49 

DF8H 

Set Point High differential in Channel 8 

150 

  2 

 

50 

DF8L 

Set Point Low differential in Channel 8 

150 

  2 

 

51 

0AJ1 

Zero adjustment of temperature sensor in Channel 1                

-50 

+50 

  0 

°C 

… 

… 

… 

… 

… 

 

 

58 

0AJ8 

Zero adjustment of temperature sensor in Channel 8                

-50 

+50 

  0 

°C 

59 

SCh1 

Activation/deactivation of Channel 1 with values (-1÷2): “-1” = channel deactivated, “0” = 

channel activated and does not belong to any average group, “1” = channel activated and 
belongs to average group No.1, “2” = channel activated and belongs to average group No.2 

 

-1 

 

 

  1 

 

… 

… 

… 

 

 

 

 

66 

SCh8 

Activation/deactivation of Channel 8

 

with values (-1÷2): “-1” = channel deactivated, “0” = 

channel activated and does not belong to any average group, “1” = channel activated and 

belongs to average group No.1, “2” = channel activated and belongs to average group No.2 

 

-1 

 

 
  1 

 

67 

AS1H 

Average Set Point High in Channel 1 

-99 

100 

 50 

  °C/mA 

68 

AS1L 

Average Set Point Low in Channel 1 

-99 

100 

-50 

  °C/mA 

… 

… 

… 

… 

… 

   

  °C/mA 

81 

AS8H 

Average Set Point High in Channel 8 

-99 

100 

 50 

  °C/mA 

82 

AS8L 

Average Set Point Low in Channel 8 

-99 

100 

-50 

  °C/mA 

83 

Ti1H 

Time-delay of Set Point High Alarm in Channel 1  

200 

  0 

sec 

84 

Ti1L 

Time-delay of Set Point Low Alarm in Channel 1  

200 

  0 

sec 

… 

… 

… 

… 

… 

 

sec 

97 

Ti8H 

Time-delay of Set Point High Alarm in Channel 8  

200 

  0 

sec 

98 

Ti8L 

Time-delay of Set Point Low Alarm in Channel 8  

200 

  0 

sec 

99 

Tia1 

Time-delay of Average Set Points High (AS1H) and Low (AS1L ) Alarms in Channel 1 

200 

  0 

sec 

… 

… 

… 

… 

… 

 

sec 

 106 

Tia8 

Time-delay of Average Set Points High (AS8H) and Low (AS8L) Alarms in Channel 8 

200 

  0 

sec 

107 

OOF1 

Drive the failure line alarm (OV F, WRC) of Channel 1 to one of the 11 outputs 

200 

  0 

sec 

… 

… 

… 

… 

… 

  … 

… 

114 

OOF8 

Drive the failure line alarm (OV F, WRC) of Channel 8 to one of the 11 outputs 

200 

  0 

sec 

115 

OS1H 

Drive the Set Point High command in Channel 1 to an output 

11 

  0 

 

116 

OS1L 

Drive the Set Point Low command in Channel 1 to an output  

11 

  0 

 

… 

… 

… 

… 

… 

 

 

129 

OS8H 

Drive the Set Point High command in Channel 8 to an output 

11 

  0 

 

130 

OS8L 

Drive the Set Point Low command in Channel 8 to an output  

11 

  0 

 

131 

OA1H 

Drive the Average Set Point High command in Channel 1 to an output  

11 

  0 

 

132 

OA1L 

Drive the Average Set Point Low command in Channel 1 to an output  

11 

  0 

 

… 

… 

… 

… 

… 

 

 

145 

OA8H 

Drive the Average Set Point High command in Channel 8 to an output  

11 

  0 

 

146 

OA8L 

Drive the Average Set Point Low command in Channel 8 to an output  

11 

  0 

 

147 

OLE1 

Drive the LED of Channel 1 to an output  

11 

  1 

 

… 

… 

… 

… 

… 

 

 

154 

OLE8 

Drive the LED of Channel 8 to an output  

11 

  8 

 

155 

HC1H 

Invert Set Point High command in Channel 1 to (Hot) or (Cool) 

 HoT / Col 

CoL 

 

156 

HC1L 

Invert Set Point Low command in Channel 1 to (Hot) or (Cool) 

         HoT / Col 

HoT 

 

… 

… 

… 

   HoT / Col 

 

 

169 

HC8H 

Invert Set Point High command in Channel 8 to (Hot) or (Cool) 

 HoT / Col 

CoL 

 

170 

HC8L 

Invert Set Point Low command in Channel 8 to (Hot) or (Cool) 

 HoT / Col 

HoT 

 

171 

MoSP 

Set Points alarms (SP1H/SP1L÷SP8H/SP8L) can function either as alarm (OFF) or as limit 
supervisor (ON) 

             ON / OFF                ON 

 

172 

OFWC 

Over Flow and Wrong Connection alarms activate (ON) or do not activate (OFF) the internal 
general relay alarm 

ON / OFF               ON 

 

173 

rP2H 

Not in use 

 

 

 

 

174 

rP2L 

Not in use 

 

 

 

 

… 

… 

… 

 

 

 

 

185 

rP8H 

Not in use 

 

 

 

 

186 

rP8L 

Not in use 

 

 

 

 

187 

rEPE 

Not in use 

 

 

 

 

188 

V-AD 

Device’s address on monitoring network 

98 

  0 

 

189 

ChM1 

Input signal type in Channel 1, values: ”1” for J sensor, “2” for K sensor, “3” for PT100 sensor 
with 3 cables,  “4” for ΡΤ100 sensor with 2 cables, “5” for 4÷20 mA and “6” for 0÷20 mA 

  1 

 

… 

… 

… 

… 

… 

 

 

196 

ChM8 

Input signal type in Channel 8, values: ”1” for J sensor, “2” for K sensor, “3” for PT100 sensor 
with 3 cables,  “4” for ΡΤ100 sensor with 2 cables, “5” for 4÷20 mA and “6” for 0÷20 mA 

  1 

 

 

3

 

Summary of Contents for ALAN-8

Page 1: ...ach channel 19 Capability to drive each of the 32 alarms to the outputs 1 11 independently or in groups 20 8 LEDs one for each channel 21 Capability to drive the LED operation to the outputs for monitoring 22 One general internal relay output 250VAC 10A for siren activation 23 Time delay for each of the 32 alarms NOTE Time delay for the Average Set Point High and Low alarms is common to each chann...

Page 2: ...11 for monitoring This adjustment is set from parameters OLE1 OLE8 If we set 0 the LED will not correspond to any output while if we set from 1 11 the LED of the respective channel is driven to the selected output 11 General internal relay alarm 250VAC 10 A resistive loads When one or more of the 32 alarms appear the general relay is activated If the parameter No 172 OFWC is set to OFF the OVER FL...

Page 3: ...Channel 8 0 200 0 sec 98 Ti8L Time delay of Set Point Low Alarm in Channel 8 0 200 0 sec 99 Tia1 Time delay of Average Set Points High AS1H and Low AS1L Alarms in Channel 1 0 200 0 sec sec 106 Tia8 Time delay of Average Set Points High AS8H and Low AS8L Alarms in Channel 8 0 200 0 sec 107 OOF1 Drive the failure line alarm OV F WRC of Channel 1 to one of the 11 outputs 0 200 0 sec 114 OOF8 Drive th...

Page 4: ...ads Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case of main power failure Accuracy 1 1 digit LCD screen 2x16 characters Operating temperature 15 70 C Storage temperature 20 80 C The devise is mounted on a panel hole with dimension 137x137mm Connection with plug in screw terminals IP protection rating IP42 front side To be installed i...

Page 5: ... parameters 4 0 20mA a cutline the general relay is activated the corresponding input s LED is flashing and the screen displays OV F b short circuit line short circuit alarm corresponds to 0mA and the reception of the alarm can be adjusted by the parameters Power failure setup An internal relay 250VAC 10A with one contact terminal blocks 34 35 is available to set up an external alarm circuit in ca...