background image

 

1011026 User Manual Issue 01 (26.10.2021) 

 

 

13 

9.

 

Technical Information 

 

Control Unit 

Model 

1002510 

Enclosure 

Dimensions: 255mm (W) x 180mm (H) x 88mm (D) 
Ingress Protection: IP65 
Material: ABS 
Lid Screws: Torque: 1.2Nm, Size: PH 2 

Operating Environment 

Operating temperature: -

20°C … +50°C

 

Relative humidity: 100% 
Altitude: 2,000m 
Pollution degree: 2 
Intended for use indoors or outdoors, and in wet locations 

Power Source 

230VAC ±10% 50Hz 
Mains isolator switch internal to unit 

Power Consumption 
(Control unit only) 

6.4W, 10.1VA, cos φ = 0.63

 

All relays energised, battery 
charging, beacon off, J6 - J9 
disconnected 

11.3W, 17.8VA, cos φ = 

0.63 

All relays energised, battery 
charging, beacon on continuously 
(not flashing), J6 - J9 disconnected 

Power Consumption 
(Control unit and 
pumps/motors and beacon) 

1.6kW, 1.8kVA, cos φ = 0.8

All relays energised, battery charging, beacon on continuously (not 
flashing) 
J6 

 Pumped outlet 

J7 

 De-sludge pump 

J8 

 Blower 

J9 

 Chemical dosing pump 

Grundfos KP 350 
Grundfos KP 250 
Secoh JDK-250 
Kingspan 404390 

Fusing 

F1 (De-sludge pump, terminals 
3&4) 

T 5A H 250V 

F2 (Internal power supply unit) 

T 2A H 250V 

F3 (Motor/blower, 5&6) 

T 3.15A H 250V 

F4 (Chemical dosing pump, 7&8) 

T 250mA H 250V 

F5 (Pumped outlet, 1&2) 

T 5A H 250V 

F6 (Beacon output, 21&22) 

500mA resettable fuse 

Electrical Safety 

IEC/EN 61010-1:2010+A1:2019, Class I, CAT II 

Battery Backup 

6V 1200mAh NiMH battery pack kept charged by on-board charger. 
Backup time at least 12 hours. 

Inputs 

3 x inputs from volt-free contacts (rotation arm, float switch and external 
alarm condition such as pressure switches in series) 
1 x blower pressure sensor (alarms below 15mB, 4mm inlet) 

Mains Outputs 

Relays only energised when mains power is present. 
Pumped outlet (1&2) 

Constant mains output, 
fused T 5A H 250V 

De-sludge pump (3&4) 

SPST relay switched, 
fused T 5A H 250V 

Motor/blower (5&6) 

SPST relay switched, 
fused T 3.15A H 250V 

Chemical dosing pump (7&8) 

SPST relay switched, 
fused T 250mA H 250V 

Telemetry Relay Outputs 

3 x volt-free SPST contacts. De-energised in alarm condition. 

Summary of Contents for Klargester 1002510

Page 1: ...Kingspan Klargester 1011026 Domestic Wastewater Control Panel USER MANUAL...

Page 2: ...Installation of High Level Alarm HLA where applicable 6 Beacon units P No 1009254 where applicable 7 Installation of High Level Alarm HLA where applicable 7 For Biotec Bioficient or BioSafe Applicati...

Page 3: ...of Practice Statutory Requirements and any specific instructions issued by the supplier of these details Earthing All equipment must be earth bonded in accordance with the latest IEE Wiring Regulation...

Page 4: ...1011026 User Manual Issue 01 26 10 2021 4 7 Installation Figure 1 1002510 Lid Cover Figure 2 Enclosure Mounting Dimensions Figure 3 Control Panel Wiring 1...

Page 5: ...1011026 User Manual Issue 01 26 10 2021 5 Figure 4 DTP Control Panel Wiring 2...

Page 6: ...tape at a depth of 150mm For loads up to 0 75kW and runs of less than 100 metres 2 5mm 3 core SWA is adequate For loads up to 1 55kW and runs of less than 100 metres 4 0mm 3 core SWA should be used I...

Page 7: ...Applications 7 7 1 Power Pressure Failure Detection System PPFDS where applicable The panel is designed to be used in conjunction with the Beacon unit to provide warning of either loss of power or ai...

Page 8: ...te socket below the battery on the PCB marked J3 After finishing wiring replace the isolator cover and screw Turn the mains supply on at the source Turn on the panel using the isolation switch It shou...

Page 9: ...vation time Alarms The conditions shown below cause an alarm message to appear on the display the beeper sounds the beacon flashes and the common alarm telemetry relay is de energised Some alarm condi...

Page 10: ...factory defaults This menu is intended for use by installation Service engineers only The menu is entered by simultaneously pressing then releasing the three buttons On entry to the menu all outputs...

Page 11: ...4 hour format The display will show Figure 13 Date Time Use and to move between date and time Pressing the button will freeze display of the clock and enter edit mode to allow the date or time to be s...

Page 12: ...ickle Charge indicates that the unit is fully charged and maintaining the battery 8 6 7 Factory Defaults This option allows the control unit to be set back to the defaults as they were when the unit l...

Page 13: ...lower J9 Chemical dosing pump Grundfos KP 350 Grundfos KP 250 Secoh JDK 250 Kingspan 404390 Fusing F1 De sludge pump terminals 3 4 T 5A H 250V F2 Internal power supply unit T 2A H 250V F3 Motor blower...

Page 14: ...y 16 x 2 character LCD Green power LED Real Time Clock Event log timestamps and controlling the operation of the motors blowers according to a timetable LED Beacon 1009254 Only the LED beacon 1009254...

Page 15: ...ay Motor Blower Start Time Time of Day where Unit is started 00 00 00 Stop Time Time of Day where Unit is stopped 23 59 59 Run Time Time for the components to Run 23 59 59 24 hours Pause Time Time for...

Page 16: ...1011026 User Manual Issue 01 26 10 2021 16 This Page Intentionally Left Blank...

Reviews: