-Gas Conversion Part A-
MQVL48 / MQVLB48
Models:
MQVL48N, MQVL48NE, MQVL48NE2, MQVL48LP, MQVL48LPE, MQVL48LPE2, MQVLB48N, MQVLB48NE, MQVLB48NE2,
MQVLB48LP, MQVLB48LPE, MQVL48BLPE2
Kit Number
Description
Pilot Orifice
Burner Orifice
Brass (1000-255)
Brass Nipple
Air Shutter
Hi/Lo Regulator
48VL-CKLP
LP Conversion
-Millivolt-
1001-P167SI
#30
(977.167)
#50
1000-253
Closed
Fully Open
1001-P202SI
(0.907.202)
48VL-CKNG
NG Conversion
-Millivolt-
1001-P165SI
#51
(977.165)
#31
1000-253
Closed
1/8”
1001-P201SI
(0.907.201)
48VL-CKLPI
LP Conversion
-IPI-
1001-P168SI
#35
(977.168)
#50
1000-253
Closed
Fully Open
1002-P014SI
(0.907.014)
48VL-CKNGI
NG Conversion
-IPI-
1001-P166SI
#62
(977.166)
#31
1000-253
Closed
1/8”
1002-P016SI
(0.907.016)
1. The Burner Tube must be removed from the Burner Pan Assembly (See
Burner Tube Removal
). Adjust the Air Shutter to the correct Primary Air
setting as specified in the manual or on the label plate. To adjust the
Primary Air setting, loosen screw on the side of the Air Shutter and rotate
to the correct opening using a drill bit or tape measure. Retighten screw.
2. Remove the Main Orifice using a ½” wrench and replace with the new
Conversion Orifice which came with the Conversion Kit.
3. Replace the Burner Tube. Install the new Pilot Orifice (See
Pilot
Conversion
) and Hi/Lo valve regulator by following instructions supplied
with the Conversion Kit.
Refer to “
Gas Specifications Chart
” for inlet pressures and input ratings. Clock meter to verify input rate. Place conversion label as
close to converted gas control as possible. Refer to lighting instructions to verify the normal operating sequence of the ignition system.
IMPORTANT: Always check for gas leaks with a soap and water solution. DO NOT USE OPEN FLAME FOR LEAK TESTING.
⚠
-Warning-
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's instructions and
all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not
followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury
or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper
and complete until the operation of the converted appliance is checked as specified in the manufacturer's instructions
supplied with the kit.
⚠
Caution
:
The gas supply shall be shut off prior to disconnecting the electrical power, before proceeding with the conversion.
Pilot Must
Maintain This
Relationship
With Burner.
Burner Mount
Air Opening
Valve
Orifice
Pilot
51