Note: Threshold high and threshold low are integer; it is 10 times the real value.
Such as you want to set the threshold low to -12.3, threshold high to 45.6, you need to enter low -123
and high 456.
[High Alarm SMS Content],[ Low Alarm SMS Content],[ Recovery SMS Content]
This device allows you to customize the content. Support up to 40 characters, the SMS content sent to
the authorized number when AIN alarmed or returned to normal.
[Enable Recovery Inform]
If checked, the device will send a message to the authorized number when AIN returns to normal.
8.6.4. DS18B20 Temperature Settings
[Sampling Period]
Range 2-65535, unit 100ms (0.1 second), by default 10, indicating that the DS18B20 temperature is
collected every 1000 milliseconds (1 second). In low power mode, it is recommended to extend the
sampling period according to actual needs, which can reduce power consumption.
[Alarm/Recovery Verify Time]
Range 0~65535 seconds, by default 2, indicates that the temperature exceeds the threshold for 2
seconds before it is confirmed as alarm or recovery, it can prevent misreporting. Set to 0 means that, if the
temperature exceeds the threshold, the alarm will be made immediately.
[Current Value]
Click read to display current temperature.
[Threshold High], [Threshold Low]
When the current temperature is between these two values, it is normal; otherwise there will be alarm;
Note: Threshold high and threshold low are integer; it is 10 times the real value.