The control unit has additional special features not required for most 
of standard installations. All descriptions are reported here below.

12.

 Backjump 

       adjustment

This procedure allows for adjusting or eliminating the backjump. 
It consists in inverting the door movement at the end of the path 
to perform belt recovery, facilitate unlocking and safeguard the 
mechanical system. On certain installations this is unnecessary, 
therefore this value can be adjusted.

DEFAULT: STAR EVO backjump = value 2, equal to 500ms

  Prior to proceeding with this progra mming procedure, 

first  verify  whether  either  the  “basic  path  programming”  or 

the “advanced path programming” have been completed.

STEP ACTION

RESULT

1

PUT THE DOOR IN THE 

CLOSED POSITION

2

PRESS THE 

START

 BUT-

TON FOR 3 SECOND

All the LEDs turn off (if not, 

consult Paragraph 14.1)

3

PRESS THE 

SET

 BUTTON 

FOR 1 SECOND

The yellow “

set

” LED 

turns on in the fixed mode 
and the red “

error

” LED 

indicates the backjump* 

level

4

PRESS THE 

SET

 BUTTON 

FOR 1 SECOND

The yellow “

set

” LED 

flashes then turns on in the 

fixed mode and the red 

error

” LED indicates the 

backjump* level

backjump value setting

5

EVERY TIME THE 

SET

 

BUTTON IS PRESSED, 
THE VALUE CHANGES 
FROM 1 TO 6 STARTING 
FROM THE CURRENTLY 
SET VALUE

1

5

2

4

3

6

example 1:
current backjump = 3
after SET is pressed, backjump = 4
example 2:
current backjump = 5
after SET is pressed 2 times, backjump = 1

The yellow “

set

” LED 

remains lit in the fixed 

mode and the gred 

error

” LED indicates the 

backjump* level

saving of the set backjump

6

PRESS THE 

RADIO

 

BUTTON FOR 2 ECONDS

The yellow “

set

” LED 

remains lit in the fixed 
mode and the red “

error

”  

LED flashes fast

7

PRESS THE 

SET

 AND 

RADIO

 BUTTONS 

SIMULTANEOUSLY OR 
WAIT 10 SECONDS TO 
EXIT THE PROCEDURE

The LEDs return to 

the normal operation 

configuration

* The backjump value is indicated by the number of flashes of the 
series based on the set value.

Backjump levels: 0 / 500mS / 700mS / 1Sec / 1,5 Sec / 2Sec.

When the series consists of one flash, the backjump value is zero (no 
inversion of movement at end-of-path), when there are 6 flashes, the 
backjump is set to the maximum value.
Clearly, the other series indicate growing intermediate values from 
1 to 6.
The backjump value can be known at any time after the SET button 
is pressed the first time, by counting the number of flashes of the 
green “photo” LED.

  If the backjump value is set too high, some undesired 

clearance may remain between the door and the mechanical 

stop.

Summary of Contents for ELEVO

Page 1: ...ELEVO EN Instructions and warnings for installation and use Made in Italy...

Page 2: ......

Page 3: ...ming of the button linkedto the on board courtesy light 13 5 4 Deleting all memorised transmitter 14 5 5 Deleting a single transmitter 14 5 6 Remote tools free transmitter programming 14 6 Programming...

Page 4: ...KING gates Customer Service Do not make alterations to the product in any way Improper use can only lead to malfunctions The manufacturer declines all liability for damage caused by arbitrary modific...

Page 5: ...ycles up to 2 16 8 2 2 4 12 6 Table 3 Limits in relation to force required to move door leaf Force required to move leaf N Cycle reduction percentage Up to 200 100 200 300 70 300 400 25 The height of...

Page 6: ...or increasing the range of the transmitters Paragraph 10 8 Pause time for automatic re closing adjustable to between 0 and 180 sec with knob Paragraph 4 2 Obstacle sensitivity adjustment with knob Par...

Page 7: ...and cause malfunc tions fire or dangerous situations If the door includes an access door make sure that it does not obstruct normal travel Fit a suitable interlock system if necessary Only insert the...

Page 8: ...8 EN 6 1 2 3 4 4a 4b 4c 7 B 5 A 12 A 10 11 E E 9 B D 8 D C 13 F...

Page 9: ...leaving the gearmotor on the ground lift the guide from the front section and secure using two screws plugs or rivets according to the installation surface 03 Secure the brackets H using the screws I...

Page 10: ...he rear mechanical stop R next to the carriage fig 23 and tighten the screw Q fully down Important Make sure the release cord can be pulled below a height of 1 8 m 23 Q R 3 3 Installation of other dev...

Page 11: ...t 1 1 2 3 4 5 6 7 8 9 10 11 12 2 3 4 ON DIP 13 14 Flash Aerial Phototest S2Photo 0 VDC STOP START 24VDC S1Edge 24VDC Lock Table 5 Terminals Function Description 1 2 Flash 24V max 15W warning light 3 P...

Page 12: ...unction is ac tivated The control unit automatically closes the leaves after the time set through the PAUSE knob see Paragraph 4 2 If the AUTO dip switch is put to OFF the automatic re closing functio...

Page 13: ...s 11 12 To use this function the Lock AUX output must be set to courtesy light see Paragraph 13 1 STEP ACTION RESULT 1 PRESS THE RADIO BUTTON FOR 1 SECOND The red radio LED turns on in the fixed mode...

Page 14: ...ot consult Paragraph 14 1 2 PRESS THE SET BUTTON FOR 1 SECOND The red radio LED flashes and the yellow set LED turns on in fixed mode 3 PRESS A BUTTON ON THE TRANSMITTER YOU WISH TO CANCEL The red rad...

Page 15: ...ding slowdown see paragraph 6 2 STEP ACTION RESULT 1 MOVE THE DOOR TO HALF WAY POSITION 2 PRESS THE SET BUTTON FOR 1 SECOND The yellow set LED flashes if not consult Paragraph 14 1 3 PRESS THE SET FOR...

Page 16: ...TON OR A BUTTON OF A PAIRED TRANSMIT TER OR CLOSE START WIRED CONTACT TO SET THE SLOWDOWN START POINT FOR NOT HAVE SLOWDOWN WAIT UNTIL THE MOVEMENT HAS BEEN COMPLETED The yellow set LED stays on in th...

Page 17: ...RED RADIO LED AND YELLOW SET LED If when attempting to enter any programming scheme the Set Radio and Error LEDs flash fast three times it means that the control unit protection is activated See Para...

Page 18: ...active during closing and opening phase This input is normally closed NC For infra red photocells and safety edges with micro switch contact The factory wire bridge connected to S2 Photo must be remo...

Page 19: ...agraph 4 1 This input is a voltage free dry contact only Connecting power to this input will void warranty TIMER FUNCTION if START contact is kept closed for in stance through a timer controlled or b...

Page 20: ...el backjump value setting 5 EVERY TIME THE SET BUTTON IS PRESSED THE VALUE CHANGES FROM 1 TO 6 STARTING FROM THE CURRENTLY SET VALUE 1 5 2 4 3 6 example 1 current backjump 3 after SET is pressed backj...

Page 21: ...t as electric lock see Paragraph 13 1 if desired program the transmitter button for the START com mand see Paragraph 5 1 At every wired or transmitter start command the light will switch on for the se...

Page 22: ...THE SET AND RADIO BUTTONS SIMULTANEOUSLY OR WAIT 10 SECONDS TO EXIT THE PROCEDURE The LEDs return to the normal operation configuration To control the AUX contact set as courtesy light a radio command...

Page 23: ...In order to carry out the check on the safety devices the connected edges must be of the resistive type with 8 2 kOhm 14 Other functions To interrupt the following programming sequences at any time pr...

Page 24: ...ol unit stops powering the mo tor s at the end of the travel 3 If not sufficient turn the POWER knob slightly clock wise and reprogram automation s movement 4 Avoid reduce slowdown travel phase see Pa...

Page 25: ...the dimensions stated in table 1 and limits specified in tables 2 and 3 ELEVO power supply 230Vac 10 50 60Hz Max absorbed power 200 W Insulation class 1 a safety grounding system is required Emergenc...

Page 26: ...EC of the European Parliament and of the Council of 17 May 2006 on machinery and amending Directive 95 16 EC recast in accordance with the following harmonised standards It is hereby declared that the...

Page 27: ......

Page 28: ...cturer s details Timbro Stamp Azienda Company Localit Address Provincia Province Recapito telefonico Tel Referente Contact person King Gates S r l Phone 39 0434 737082 Fax 39 0434 786031 info king gat...

Reviews: