ES2 Electronic Liquid Level Transmitter

EX-1832

Calculating Milliamp Output

The King-Gage Electronic Sensor is factory-calibrated to
nominal range only.  Since there is no appreciable degree
of span adjustment, the milliamp output of the sensor at
full tank level will generally be less than 20.00 mA.

Actual output can be calculated based on total tank depth
and specific gravity of the liquid product:

(

B

 - 

A

) x 

C

= Tank Pressure

27.6807

where ...

A

 = Reserve (inches of depth from low point of tank

       to sensor)

B

  = Full Tank (inches of depth from low point of tank

       to full)

C

  = Specific Gravity of Tank Contents

Now, using the calculated tank pressure from above, the
actual milliamp value at full can be determined:

(16 x Tank Pressure) + 4 = mA Output

NOMINAL psig RANGE

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

MODEL/RANGE

5701-1-15 PSIG

Sensor

Assembly

B

A

Tank

Milk

1.032 sp. gr.

Example - mA Output Calculation for Tank Gauging
Application

The following example shows how the milliamp output of
the sensor at full tank can be calculated. The “Reserve”
represents the distance from the lowest point on the
bottom of the tank to the installed sensor.  “Full” is the level
of contents at which the tank is filled to capacity.  The liquid
contents of the tank is milk @ 1.032 sp.gr. The sensor
installed is a nominal 15 psig range model.

C

 = 1.032 (specific gravity)

B

 = 400 in. (full level)

A

 = 28 in. (reserve)

(400 - 28) x 1.032 = 13.87 psig

27.6807

(16 x 13.87)  + 4

= 18.79 mA

15 PSIG

3201 South State St., Ann Arbor, Michigan 48108-1625 U.S.A.

PO Box 1228, Ann Arbor, Michigan 48106-1228 U.S.A.

Phone: (734) 662-5691 • FAX: (734) 662-6652

www.king-gage.com

C O R P O R A T I O N

E N G I N E E R I N G

KING

®

Since 1937

Summary of Contents for ES2 550*-1 Series

Page 1: ...id Level Transmitter EX 1832 Effective August 2004 EX 1832 KING GAGE 4 20 mA Remote Liquid Level Transmitter ES2 Remote Liquid Level Transmitter Model 550 1 w Cable and Junction Enclosure Installation and Operation Instructions ...

Page 2: ...y at Ann Arbor Michigan within ten days of discovery of the defect No other warranties whether expressed implied or statutory including the warranties of fitness for a particular purpose or merchanta bility are given by this agreement The exclusive remedy for nonconformity of these goods shall be repair and or replacement of the nonconforming goods or parts Seller will not be liable for consequent...

Page 3: ...ro adjustments and signal loop connection terminals Range Designation A model number range designation is listed on the end of the transmitter housing The last two digits of the model number actually refer to the transmitter range As an example MODEL 5502 1 10 is a 0 10 psig range standard mount transmitter Model No Designations 55xx 1 xx Pressure Range 05 0 5 psig 10 0 10 psig 15 0 15 psig 30 0 3...

Page 4: ... 550 1 9 891 in 251 mm 8 875 in 225 mm MODEL 550 1 7 625 in 194 mm 2 250 in 57 mm Signal Junction Enclosure 4 33 in 110 mm YEL GRN WHT BLK RED 4 20 mA OUTPUT ZERO SPAN CAUTION METER KING GAGE Electronic 4 20 mA Sensor 2 96 in 75 mm Mounting holes 2 3 23 in 82 mm Model 5501 Short Mount Model 5503 Long Mount Model 5502 Standard Mount ...

Page 5: ... the supplied cable length will allow DO NOT SPLICE additional cable onto the transmitter Seal plugs caps are supplied with the Junction Enclo sure These are intended to be installed over the mounting hole provisions to seal the mounting hardware openings Note that mounting fasteners are not fur nished and must be supplied by customer Sensor Cable Rubber Ferrule Locking Nut Detail Mounting Junctio...

Page 6: ... Look for 10 to 12 twists per foot Use shielded cable with the shield connected to circuit common at one end only Never run signal carrying wires in the same conduit that carries power lines relay contact leads or other high level voltages or currents The signal output is transmitted through 4 20 mA current loops that are low impedance electric circuits Long cabling runscanincreasethesusceptibilit...

Page 7: ...e previous page that permit accurate reading without disturbing the signal loop wiring Important Set meter for DC current mA or 001 Amp scale Internal resistance through the meter must be 20 ohms or less Higher resistance values will erroneously show lower milliamp reading on meter Note Always re install cover when done Sensor Cable The transmitter cable contains five 5 individual wires that are t...

Page 8: ...ned 16 x Tank Pressure 4 mA Output NOMINAL psig RANGE MODEL RANGE 5701 1 15 PSIG Sensor Assembly B A Tank Milk 1 032 sp gr Example mA Output Calculation for Tank Gauging Application The following example shows how the milliamp output of the sensor at full tank can be calculated The Reserve represents the distance from the lowest point on the bottomofthetanktotheinstalledsensor Full isthelevel of c...

Reviews: