PNEUMATIC LEVEL CONTROLLER
PNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
15
www.kimray.com
Maintenance - Filter
Filter - Disassembly
Step 1 – Shutoff supply pressure to controller and bleed
supply line
Step 2 – Remove the supply line from the filter and
remove the filter from the controller
Step 3 – Clean out filter element. Using compressed air
in the downstream (male) connection will help to ensure
debris is dislodged.
Step 4 – Reinstall filter.
Direction of air flow
to clean filter element