Q. Can the Sirius Module be installed standing vertically with the connection facing up without
potentially stressing the cells inside the Module?
A. Yes, but NOT in a movable\vibrating position.
Q. What is the difference between the ‘’balancing “and “auto balancing” in “set Config” tab in
SiriusVIEW?
A. Balancing: Balancing can be activated from any voltage level when the Module is in standby mode
(Zero current). When all the cells get balance, the balancing will stop. The time required to balance all
cells depends on cells condition.
Auto balancing: Auto balancing is activated automatically during charging when the cells get
unbalanced.
Note that it is activated only when the Module Voltage reaches ~52 V.
Q. Can balancing and auto balancing options be activated at a same time?
A. Yes.
Q. When to use Sirius Config?
A. The Module is received with full settings and the most updated firmware, however, if you want to
calibrate parameters (current, voltage, date and time, alarm, temperature) you can use Sirius Config
for calibrating. For more information contact your Reseller.