Sirius Capacitor Module
–
User Manual
Model Number - 3550-48-B-1.7C-TM-SD-A-19G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
24
6.2 Series Connection of Sirius Modules:
A maximum of 8 Modules can be connected in Series with a Module Combiner.
•
Steps to Connect Modules in Series:
Refer to the Series combination of the Sirius Modules as shown below and make your connection
accordingly.
•
Connect the
negative (-)
of the
F12 Terminal
of the first Module with the
positive (+)
of the
F12
terminal
of the next Module.
•
Take the Output Positive from
first
Module and Output Negative from the
last
Module.
Caution!
Charge all the Modules to 100% SOC or same voltage level before
connecting them in Series.
Note!
Switch ON the bypass Circuit breaker when connecting in Series, otherwise
it will damage the electronic switch.
Note!
Modules cannot be connected in series-parallel combination under any
circumstance.
Caution!
The Bypass circuit breaker is not protected with electronic switch,
therefore during over-voltage, under voltage and high temperature
conditions, the terminals will not shutdown. It only gives protection for
over current condition.