For information about operating the Sol-Ark Hybrid inverter, see the SOl-Ark Owner’s Guide .
6. Single System Installs: Install Double Pole 50A breaker in Main Panel for Grid In/Out
a. It is best practice to install at the opposite end of the bus bar from the main breaker
(Usually this is the bottom of the breaker panel as seen on page 5).
7. Multi System Installs: Line side tap recommended for grid connection point
a. Please see page 15 for an example diagram.
8. Mount Sol-Ark 12K
a. Find a suitable location for the system(s), keeping in mind the dimensions in Fig.
below.
b. System must be protected from moisture and extreme heat. (Do not mount outdoors
or in attic OR WARRANTY WILL BE VOID AND DAMAGE WILL LIKELY
OCCUR)
c. The system weighs 74lbs (34kg), be sure to attach it securely to the wall. You may
need to affix a mounting board to your wall first using 6-8 screws into studs.
d. Then use 2-3 screws (appropriate in length and type for your mounting surface) to
mount the French Cleat to the board/wall (washers recommended).
e. Mount the Sol-Ark on the installed cleat making sure that it sits properly and is level.
f. Add 2 screws in bottom mounts.
Sensor Pin Out (Located in Sol-Ark user area)
Batt Temp:
Battery Temperature Sensor has
no polarity and is needed for voltage correction
when using lead acid batteries.
CT1 & CT2:
Current transformers used for limit-
ed to home mode and peak shaving
RSD 12V:
12V power supply for RSD transmit-
ters such as TIGO and Midnite
Gen Start Relay:
Two wire start for generators,
simple open or closed relay
Gen On Relay:
Not currently used