background image

A

Page 2 / 24

Product Description

RBW322-FTL

Datasheet 1.10-60.015-01-EN

Issue 2016-05-16 ab V2.60

Important Information Regarding Product Safety

Safety Instructions

This data sheet contains information on installing and commissioning the product "RBW322-FTL". 
Each person who carries out work on this product must have read and understood this data sheet. If 
you have any questions that are not resolved by this data sheet, you can obtain further information 
from the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device.  Within the EU, these 
include regulations regarding occupational safety and accident prevention as well as those from the 
VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other 
countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified 
technicians. Qualified technicians are persons who are familiar with the described product and who 
can assess given tasks and recognize possible dangers due to technical training, knowledge and 
experience as well as knowledge of the appropriate regulations.

Legend

WARNING

Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.

CAUTION

Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.

!

NOTICE

Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not 
avoided.

NOTE

Indicates additional information that can simplify the work with the product for you.

Notes on Disposal

For disposal, the product is considered waste from electrical and electronic equipment (electronic 
waste) and must not be disposed of as household waste. Special treatment for specific components 
may be legally binding or ecologically sensible. The local and currently applicable legislation must be 
observed.

Summary of Contents for RBW322-FTL

Page 1: ...EP D2 10 01 for connection to an EnOcean gateway In combination with the MD15 FTL xx the RBW322 FTL constitutes a functional unit for controlling the room temperature You can find information about the protocol description on the EnOcean Technology website http www enocean alliance org en enocean_standard Content Page Important Information Regarding Product Safety 2 Technical Data 3 Dimensions 4 R...

Page 2: ...operator to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training knowledge and experience as well as knowledge of the appropriate regulations Legend...

Page 3: ...mperature units selected 7 0 35 0 C in 0 5 K increments or 44 95 F in 1 F increments Controls Push and rotary knob for setting setpoint party mode vacation mode weekly schedule time date display options e g 12 24 hour display and service data Occupancy button manually switch between present absent Interfaces technoLink radio interface Radiogram EnOcean radiogram bidirectional Frequency 868 3 MHz D...

Page 4: ...A Page 4 24 Product Description RBW322 FTL Datasheet 1 10 60 015 01 EN Issue 2016 05 16 ab V2 60 Dimensions 3 6 3 5 0 4 0 4 0 8 0 2 6 5 0 3 R 1 8 0 1 ...

Page 5: ...rectional and includes an intelligent synchroni zation process If the radio communication between the RBW322 FTL and the MD15 FTL xx is interrupted an internal resynchronization procedure starts automatically Radio connection Gateway operation Gateway and pair operation Pair operation EnOcean Gateway RBW322 FTL EnOcean Gateway RBW322 FTL MD15 FTL RBW322 FTL MD15 FTL ...

Page 6: ...materials and screening elements e g suspended ceiling elements installation shafts fire doors etc must be taken into consideration during planning NOTICE Elevated humidity increases natural signal damping NOTE Recommendation Plan radio paths horizontally on a single level with max 30 m between the trasmitting and receiving modules Designed only for use in rooms Observe minimum distances to potent...

Page 7: ...tallation location can be changed and optimized at any time without additional effort Mounting The installation location must have sufficient lighting using the device in unlit rooms such as interior kitchens bathrooms shortens the length of the maintenance cycle The solar cell is optimized for indoor use and it works particularly efficiently with diffuse lighting NOTICE Prolonged illumination at ...

Page 8: ...8 24 Product Description RBW322 FTL Datasheet 1 10 60 015 01 EN Issue 2016 05 16 ab V2 60 Wall mounting Flexible adhesive mounting with double sided transparent adhesive strips Removal 1 2 3 4 5 6 7 1 2 3 4 5 ...

Page 9: ...d malfunction message see page 22 12 24 hour display or the number of the usage time 6 Radio communication indi cator Radio symbol visible Radio symbol not visible Radio symbol flashing Radio communication present at least one radio partner has been taught in No radio communication present no radio partners have been taught in or all radio partners are malfunctioning Radio telegram in transmission...

Page 10: ...witching point start time for comfort mode Item Designation Explanation 1 Display Displays information regarding the current status 2 Push and rotary knob Turn set value e g setpoint Turn counterclockwise reduce value Turn clockwise Increase value Press change levels or confirm display setting 3 Solar cell Generates energy for the room control module 4 Magnetic contact below the housing Switches t...

Page 11: ...cupancy button for approximately 5 s switches summer mode on or off Manually switching between comfort and economy mode You can manually switch between comfort mode and economy mode and vice versa by pressing the Occupancy button This is displayed by the comfort mode or economy mode icons The Auto icon also disappears from the display NOTE The manually adjusted operating mode remains active until ...

Page 12: ...ial display A new setpoint can also be applied by pressing the push and rotary knob briefly Manuall override will also make the Auto symbol disappear NOTE The manually adjusted setpoint remains active until the next usage time status change The sepoints for comfort mode and economy mode which were set on the configuration level become active then see page 16 and the Auto symbol is displayed again ...

Page 13: ... usage time extension Set the end time for party mode usage time extension turning the knob The selected comfort mode extension usage time extension is shown in the display by the bar indicator Confirm the entry by briefly pressing the knob The display switches back to the initial display The comfort mode extension is effective immediately and comfort mode is switched on The activated party mode i...

Page 14: ...f the vacation Confirm the setting by pressing the knob The display switches back to the initial display Vacation mode begins on the set start date at 00 00 midnight and ends on the set end date at 00 00 midnight If a vacation time is set and has not yet begun the icon is shown on the initial display If vacation mode is active the vacation end date and the icon are shown on the display If vacation...

Page 15: ...ond usage time Set the second third and fourth usage times if desired The setting procedure is the same as for the first usage time block The display also shows which usage time block 1 is set The set utilization times will be saved after 10 s of idle time without further input when 4 utilization times were entered or end time start time The usage times of the current day are shown by the bar indi...

Page 16: ...g the knob Setting the time and date Press the knob for 3 s Use the knob to select the Time Date function TIME and press the knob The hour minutes year month and day can then be set in sequence The values to be set are always flashing Set the time Set the hour Confirm setting by pressing the knob Set the minutes Confirm setting by pressing the knob Set the year Confirm setting by pressing the knob...

Page 17: ...l display Default setting Initial display temperature Setting the 12 24 hour display Press the knob for 3 s Use the knob to select the 12 24 hour display function 24h and press the knob Set 12 or 24 hour display Confirm the setting by pressing the push and rotary knob If the 12 hour display 1 is activated an additional A for AM or P for PM is shown in the display Default setting 24h Switching the ...

Page 18: ... room control module changes to the service level Using a magnet Briefly press the magnet against the upper right hand side of the device see figure The room control module changes to the service level The following functions are available on the service level Registration Function Delete Function Status display for taught in radio partners Valve position for service purposes Restore default setti...

Page 19: ...dicator of the radio partner Turning the knob displays these status messages for every taught in radio partner in sequence Valve Position for Service Purposes In the service level use the knob to select the Valve position for service purposes SERV function Press the knob Turn the knob to select the desired valve position Confirm the setting by pressing the knob The display switches to the initial ...

Page 20: ...he specific settings and functions of the RBW322 FTL In addition to these instructions the product descriptions of the MD15 FTL xx radio partner and EnOcean gateway must also be observed Select service level see page 18 Use the knob to select the Teach in function T IN Teach in wireless actuator Up to 4 MD15 FTL xx radio actuators can be taught in on the RBW322 FTL Use the knob to select the Teach...

Page 21: ...n NOTE After a successful teach in process the device ID of the radio partner is stored in the SolarFunk room control module The teach in process does not need to be performed again when the battery is changed If the teach in process fails the radio symbol is not visible on the display The teach in process must be performed again or the radio communication path must be checked See chapter General ...

Page 22: ... of time the display switches to This warning disappears once the communication to the missing wireless part ner is re established If the wireless communication to all taught in wireless partners is interrupted the wireless icon is no longer displayed Wireless communication with at least one taught in MD15 FTL xx wireless part ner has been interrupted for more than four hours and a resynchronizati...

Page 23: ...s see p 19 The Δ8 icon disappears from the display Register the radio partner again The RBW322 FTL has a serious malfunction if the Δ8 icon continues to appear It should be checked by an authorized service technician System time The RBW322 FTL s internal system time is monitored constantly The Δ3 icon appears on the display if a system time malfunction is detected in the RBW322 FTL Reset the time ...

Page 24: ...Savings Time Flag bit When activating deactivating this function the RBW322 FTL does not automatically detect whether the time should be adjusted straight away or not The time should be synchronized immediately after making this kind of changes Date and Time Setting If the defined validity ranges are exceeded the dates and times transmitted by the gateway are rounded up or down to the valid ranges...