Datasheet 2.50-60.003-01-EN

FBR3

Product Description

Issue 2016-01-05

Item

Technical Data

Accessories (not included in delivery)

FBR3

Fieldbus loop controller for individual room control with 2 continuous output signals 
DC 0 V to 10 V.

Nominal voltage

DC 12 V ±20%; 1,6 W

Inputs

Room sensor with KP10 measuring system (2.73 V at 0 °C; TC = 10 mV/K)
Remote adjuster for setpoint correction (10 k

)

3 digital inputs for voltage-free contacts, configurable for program time 
extension, presence detector, window contact, fault message, operating 
message, etc.

Outputs

2 continuous outputs DC 0 to 10 V, max. 5 mA
1 “Plant On” relay output; voltage-free changeover switch AC 230 V; 
8 (3) A
1 transistor output for LED display; DC 12 V, 2 mA

Bus connection

Fieldbus, max. 2000 m

Address switch

Addressing 01–63 by means of 2 rotary switches in the housing

Displays

2 LEDs

LED data: flashes during fieldbus data transmission
LED error: lights up in case of fieldbus error

Housing

Plastic housing, cover color RAL 9010 (pure white)

Installation

Mounted on wall or on flush-mounted box

Degree of protection

IP20 

Protection class

II in accordance with EN 60730

Ambient temperature

0 to 45°C

Ambient humidity

20.. 80 % r.h., non-condensing

Weight

0.60 kg

Dimensions

WxHxD mm 154x83.4x35

Z19

Standard rail bracket clip
For mounting on TH35-7.5 top hat rail

Summary of Contents for FBR5

Page 1: ...ⶹ㗠ᬍࡼⱘᴗ Product Description FBR3 Room Controller Application The FBR5 Rom Controller are used within the DDC3000 and DDC4000 automation systems for individual room control With 2 continuous output signals DC 0 V to 10 V for sequential control The fieldbus is used for data communication with the DDC3xxx DDC4xxx controller DDC software menus such as optimize heating limiting value and Y Set can exten...

Page 2: ...comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training knowledge and experience as well as knowledge of the appropriate regulations Legend WARNING Ind...

Page 3: ... continuous outputs DC 0 to 10 V max 5 mA 1 Plant On relay output voltage free changeover switch AC 230 V 8 3 A 1 transistor output for LED display DC 12 V 2 mA Bus connection Fieldbus max 2000 m Address switch Addressing 01 63 by means of 2 rotary switches in the housing Displays 2 LEDs LED data flashes during fieldbus data transmission LED error lights up in case of fieldbus error Housing Plasti...

Page 4: ... 4 5 6 7 8 9 10 11 14 15 16 21 23 24 25 26 27 28 29 30 31 32 33 K1 K2 K3 K4 230V AC 8 3 A V 1 Y V 1 Y 0 V AC DC Y2 0 10 VDC 24 V AC Y1 0 10 VDC K5 0 V 12 V DC 12 VDC CAN CAN ϑ KP10 10KΩ 3 2 1 LED 12 V 2 mA FBR3 M M 29 30 31 32 12 VDC FBR3 20 19 18 17 DDC3000 29 30 31 32 12 VDC FBR3 20 19 18 DDC4000 40 39 38 DDC4000 CAN1 CAN2 ...

Page 5: ... Mounting and Installation WARNING Contact with live parts of electrical domestic installation can cause death due to electric shock Mounting removal may only be carried out when power is switched off Wall mounting Flush mounting 1 2 3 4 3 5x35 5 6 7 01 63 8 9 10 1 2 3 4 01 63 5 6 ...

Page 6: ...n the power the FBR3 functions in the self control program See chapter self control program page 6 self control program Use without a controller is possible The self control program is then responsible for the control functions of the FBR3 To use the self control program set the fieldbus address to 00 See chapter Setting the Fieldbus Address page 6 Use of the self control program is indicated by t...

Reviews: