Product Description

DCS2501

Datasheet 2.50-12.501-01-EN

Issue 2014-05-20

Dimensions

Connection

P90

P90 uses RS232 as its bus. RS232 is specified in ANSI EIA/TIA-232-F.
To connect the RS232 bus, use a shielded pair of wires for the data lines (RX and TX) and an 
additional wire for signal ground (GND).
The maximum cable length for RS232 is 15 m for standard cables, e.g. JY(ST)Y cables with 
100 pF/m. If you need to cover larger distances, use a cable with a low capacity. A cable with half the 
capacity has twice the maximum length.
Example calculation: A Cat7 cable with 40 pF/m allows a length of 15 m • 100 pF / 40 pF = 37.5 m

71,8

0,

09

60,0

44,7

13 14

0V

3

2

1

RJ45

Ethernet

RS232

GND

RX

TX

24V~

24V=

12V=

12V=

24V=

0V

24V~

3

2

1

RS232

GND

RX

TX

GND

TX

RX

DDC3010

DDC3100

DDC3035

30

29

31

GND

TX

RX

DDC3002

DDC3003

DDC3200

DDC3300

59

58

60

3

2

1

RS232

GND

RX

TX

GND

TX

RX

HRP/LRP

31

32

33

Summary of Contents for DCS2501

Page 1: ...fenntartjuk ֱ 㒣䗮ⶹ㗠ᬍࡼⱘᴗ Product Description DCS2501 Gateway Internet Application The DCS2501 is an Ethernet gateway in System 3000 It allows you to connect to a remote BMS via the Internet The DCS2501 features a P90 interface for direct communication with a DDC3000 an HRP or an LRP The DCS2501 enables you to replace an existing modem connection with an Internet connection Content Page Important Inf...

Page 2: ... to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training knowledge and experience as well as knowledge of the appropriate regulations Legend WARNING...

Page 3: ...P90 Reset button Interfaces P90 Screw terminal RS232 Ethernet RJ45 sokket 100BASE T 10BASE T Housing Base Plastic PC black Hood Plastic PBT orange RAL 2009 Overvoltage category III Rated impulse voltage 800 V Level of contamination 2 How It Works Protection class Degree of protection Ambient temperature Ambient humidity Type 1 III IP20 0 50 C During operation 20 to 80 r h non condensing Out of ope...

Page 4: ...2 is 15 m for standard cables e g JY ST Y cables with 100 pF m If you need to cover larger distances use a cable with a low capacity A cable with half the capacity has twice the maximum length Example calculation A Cat7 cable with 40 pF m allows a length of 15 m 100 pF 40 pF 37 5 m 71 8 0 0 9 60 0 44 7 13 14 0V 3 2 1 RJ45 Ethernet RS232 GND RX TX 24V 24V 12V 12V 24V 0V 24V 3 2 1 RS232 GND RX TX GN...

Page 5: ...et 2 50 12 501 01 EN DCS2501 Product Description Issue 2014 05 20 Mounting NOTICE Mount or remove only when power is switched off Removal NOTICE Mount or remove only when power is switched off EN 50022 1 2 3 4 1 2 3 4 5 6 ...

Page 6: ...Data 5 LED Ethernet Link LED Color Signal Meaning LED RS232 Error 1 Red Remain lit No P90 connection LED RS232 Data 2 Green Flickering Data being transferred LED Power 3 Green Flashing Device is starting running a firmware update Remain lit Device is ready LED Ethernet Data 4 Yellow Flickering Data being transferred LED Ethernet Link 5 Green Remain lit Connection OK 1 2 3 4 5 ...

Page 7: ...state is restored 1 Reset button Restart Ziehen Sie den Ethernet Stecker vom Gerät ab Dadurch werden Störungen des Netzwerks vermieden Drücken Sie kurzzeitig den Reset Taster im Loch z B mit einer Büroklammer Es wird ein Neustart durchgeführt Reset NOTICE Pressing the reset button for longer deletes all the DCS2501 s settings and restores it to its initial state Disconnect the Ethernet connector f...

Page 8: ... Ethernet MTU should be 1500 bytes DSL routers often use a smaller MTU If this is the case the Ethernet packets from the DCS2501 and the BMS are sent in fragmented form Adjusting the router s MTU improves the performance If the IP address is assigned via DHCP the BMS must have a fixed IP address This fixed IP address will be provided to the Kieback Peter representative setting up the BMS The follo...

Page 9: ...P address of the DCS2501 In the default settings http 192 168 1 1 Select a language by clicking on a flag below the menus in the web interface The configuration is available in German and English Log on to the DCS2501 Select the Logon Logoff menu Select User 3 Enter the password Rights concept User 1 Users are automatically User 1 when the DCS2501 s web server is called up Or After every logoff th...

Page 10: ...nformation Click the Save button A message appears saying the settings will not be applied until the next time the device is restarted Enter the device setting information NOTE For configuration via NAT the WAN IP address of the BMS s router must be used in the device settings of the DCS2501 For configuration via NAT the WAN IP address of the DCS2501 s router must be used in the device settings of...

Page 11: ... Deactivated The DCS2501 is not integrated into the network not active Click the Save button A message appears saying the settings will not be applied until the next time the device is restarted Restart the device To do so click on System restart in the menu bar Configuring the controller Configure the following parameters in the DDC3000 NOTE The parameter 2055 01 allows you to check the communica...

Page 12: ...nning template DCS2501 on page 13 NOTE If multiple DCS2501s are used on one BMS a unique DCS identification must be assigned to each DCS2501 A valid identification consists of max 10 characters Valid characters are A Z a z or 0 9 NOTE For configuration via NAT the routers IP address must be used Type P90 Subtype LRP HRP DDC3000 Connection DCS2501 BMS active DCS2501 DCS active DCS identifica tion E...

Page 13: ...rator Protocol the information in this table Tab 1 Planning template DCS2501 DCS2501 DCS ID See chapter Configuring the BMS page 12 Operating mode connection See Section Operat ing mode on page11 BMS aktive DCS aktive Deactivated IP configuration Manual DHCP Manual IP address Network mask Gateway Host name DDC3000 HRP LRP Baud rate BMS IP address of the BMS ...

Page 14: ...A Page 14 14 Product Description DCS2501 Datasheet 2 50 12 501 01 EN Issue 2014 05 20 ...

Reviews: