Datasheet 2.50-12.501-01-EN
DCS2501
Product Description
Issue 2014-05-20
Operating mode
The following settings can be chosen as the operating mode:
■
BMS active
–
BMS active means that the BMS establishes the connection to the DCS2501.
–
The DCS2501requires a fixed IP address.
■
DCS aktiv
e
–
DCS active means that the DCS2501 establishes the connection to the BMS.
–
The BMS requires a fixed IP address.
■
Deactivated
–
The DCS2501 is not integrated into the network (not active).
►
Click the “Save” button.
A message appears saying the settings will not be applied until the next time the device is
restarted.
►
Restart the device.
►
To do so, click on “System restart” in the menu bar.
Configuring the controller
►
Configure the following parameters in the DDC3000:
NOTE
The parameter 2055/01 allows you to check the communication of the DDC3000 to the BMS via the
DCS2501.
Parameter
Value
4599/01 =
ON
4600/01 =
Baud rate
See table "Planning template DCS2501", on page 13
2051/01 =
DST mode
2031/01 =
P90
The modem menu must be deactivated.