4 / 4
P/N 3101788-EN • REV 03 • ISS 16FEB16
Specifications
Voltage
24 VDC
Current
Standby
Alarm
23 mA
29 mA
Remote microphone input
Isolated and supervised
AUX input
Impedance
Level
Frequency response
1 kΩ
0.2 VRMS to 1.0 VRMS
100 Hz to 4 kHz
Ground fault impedance
10 kΩ
Wire size
18 to 12 AWG (2.5 to 1.0 mm²)
Audio channels
4 simultaneous
Audio inputs
Local microphone
Remote microphone
Firefighter telephone
Remote audio
Isolated and supervised
Isolated and supervised
Isolated and supervised
Isolated and supervised
Messages
Storage
Length
2 min
39 s max.
Controls and indicators
Common
Paging Volume
Ready To Page
Paging Microphone
All Call
All Call Minus
Indicates relative signal strength
during active page
Flashes during preannouncement
tone, steady when ready to page
Activates/deactivates page to all areas
Activates/deactivates page to areas
not receiving EVAC or Alert message
Page To Evac
Page To Alert
Firefighter Phone
Page By Phone
Buzzer Silence
Activates/deactivates page to areas
currently receiving EVAC message
Activates/deactivates page to areas
currently receiving Alert message
Activates/deactivates remote
firefighter telephone to paging channel
Silences call-in request buzzer
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Regulatory information
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Environmental
class
UL: Indoor dry
Contact information
For contact information, see www.kiddelifesafety.com.
© 2016 Walter Kidde Portable Equipment, Inc.