• Locate the first alarm in the immediate area of the bedrooms. Try

to monitor the exit path as the bedrooms are usually farthest
from the exit. If more than one sleeping area exists, locate addi-
tional alarms in each sleeping area.

• Locate additional alarms to monitor

any stairway as stairways act like
chimneys for smoke and heat.

• Locate at least one alarm on every

floor level.

• Locate an alarm in every bedroom.

• Locate an alarm in every room where

electrical appliances are operated (i.e.
portable heaters or humidifiers).

• Locate an alarm in every room where

someone sleeps with the door closed.
The closed door may prevent an
alarm not located in that room from
waking the sleeper.

• Smoke, heat, and combustion prod-

ucts rise to the ceiling and spread
horizontally. Mounting the smoke
alarm on the ceiling in the center of
the room places it closest to all points
in the room.  Ceiling mounting is pre-
ferred in ordinary residential construc-
tion. 

• When mounting an alarm on the ceil-

ing, locate it at a minimum of 4” (10
cm) from the side wall (see figure 1).

• When mounting the alarm on the

wall, use an inside wall with the top
edge of the alarm at a minimum of
4” (10 cm) and a maximum of 12”
(30.5 cm) below the ceiling (see fig-
ure 1).

Contents of This User’s Guide

1.

Recommended Locations for Smoke Alarms

2.

Locations to avoid

3.

Installation Instructions

4.

Operation and testing

5.

Nuisance Alarms

6.

Maintenance

7.

Limitations of Smoke Alarms

8.

Good Safety Habits

9.

NRC Information

10.

NFPA Protection Standard 72

11.

California State Fire Marshal Required Information

12.

Service and Warranty

1. Recommended Locations for Smoke Alarms

This alarm detects products of combustion using the ionization
technique. It contains 0.9 microcurie of Americium 241, a radioac-
tive material (see section 9). Distributed under U.S. NRC License No.
32-23858-01E. Manufactured in compliance with U.S. NRC safety
criteria in 10 CFR 32.27. The purchaser is exempt from any regula-
tory requirements. Do not try to repair the smoke alarm yourself.
Refer to the instructions in section 12 for service.

Smoke alarms are devices that can provide early warning of possible fires
at a reasonable cost; however, alarms have sensing limitations.
Ionization sensing alarms may detect invisible fire particles (associated
with fast flaming fires) sooner than photoelectric alarms. Photoelectric
sensing alarms may detect visible fire particles (associated with slow
smoldering fires) sooner than ionization alarms.  Home fires develop in
different ways and are often unpredictable. For maximum protection,
Kidde recommends that both Ionization and Photoelectric alarms be
installed.

LOSS OF POWER (AC AND BATTERY BACKUP) TO THE ALARM
WILL RENDER THIS ALARM INOPERATIVE.
ELECTRICAL RATING:

120 VAC, 60HZ, 30mA maximum per alarm

(maximum 30mA for originating unit with 18 devices interconnected).

Product Specifications

FIGURE 1

FIGURE 3

FIGURE 2

Summary of Contents for KN-SMFM-i

Page 1: ...TTENTION Please take a few minutes to thoroughly read this user s guide which should be saved for future reference and passed on to any subsequent owner Smoke Alarm User s Guide Model KN SMFM I 120V A...

Page 2: ...TRICAL POWER IT WILL NOT WORK WITHOUT POWER MODELS WITHOUT BATTERY BACKUP WILL NOT OPERATE DURING POWER FAILURE Smoke Alarm Procedure NEVER IGNORE THE SOUND OF THE ALARM Smoke alarms are designed to m...

Page 3: ...ns 4 Operation and testing 5 Nuisance Alarms 6 Maintenance 7 Limitations of Smoke Alarms 8 Good Safety Habits 9 NRC Information 10 NFPA Protection Standard 72 11 California State Fire Marshal Required...

Page 4: ...acket is equipped to accommodate a 3 5 inch hole spacing on a round electrical box and a double gang rectangular electrical enclosure All connections should be made by a qualified electrician and all...

Page 5: ...VER TIGHTEN THE BRACKET SCREWS ENSURE THE MOUNTING BRACKET IS NOT DEFORMED OR STRESSED ONCE IT IS INSTALLED USE ONLY MOUNTING HARD WARE PROVIDED USE OF ANY OTHER MOUNTING HARDWARE MAY CAUSE THE UNIT T...

Page 6: ...s over ridden and the green LED will function to indicate either AC power is present or Battery backup operation Hush mode The green LED will blink every 3 seconds indicating the smoke alarm is in the...

Page 7: ...ttery backup will not operate if the AC power has been cut off such as by an electrical fire or an open fuse Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are...

Page 8: ...ere required by applicable laws codes or stan dards for the specified occupancy approved single and multiple station smoke alarms shall be installed as follows 1 In all sleeping rooms Exception Smoke...

Page 9: ...M THE SALE OF THIS SMOKE ALARM OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUBSID...

Page 10: ...QUESTIONS OR FOR MORE INFORMATION Call our Consumer Hotline at 1 800 880 6788 or contact us at our website at www kidde com Kidde 1016 Corporate Park Drive Mebane NC 27302...

Reviews: