![background image](http://html1.mh-extra.com/html/kidde/kir-phd/kir-phd_installation-sheet_1965306002.webp)
2 / 2
P/N 3102533-
EN • REV 001 • ISS 15AUG17
To perform an initial installation test:
1. Remove the detector from its base and verify that the proper
detector address, trouble signals, and messages are reported.
2. For KIR-PHD detectors placed in the air ducts, verify that the
airflow is within specifications. See
3. If wired for Class A operation, verify that the detector continues to
operate first with SLC_IN disconnected, reconnect SLC_IN and
then with SLC_OUT disconnected. (Refer to the installation sheet
for the base.)
4. Place a momentary ground fault on the SLC circuit to verify
operation of the ground fault detection circuitry.
5. Run a system detector sensitivity report on all detectors and verify
that readings fall within acceptable limits.
6. Perform a sensor function test, as described below.
To perform sensor function tests:
1. If desired, use the fire alarm control panel to put the detector or
zone into a service group for testing. (Refer to the panel technical
reference manual for instructions.)
2. Activate the smoke sensor using No Climb Products model Smoke
Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol
spray, a smoke generator, or the Testifire detector tester per the
manufacturer’s instructions.
3. Activate the heat sensor using a hair dryer (maintaining a distance
of three inches) or using a Testifire detector tester per the
manufacturer’s instructions.
Maintenance
To ensure proper operation, plan maintenance (regular or selected) of
the detector in accordance with the AHJ and all applicable governing
laws, codes, or standards. Refer to CAN/ULC-S536
Standard for the
Inspection and Testing of Fire Alarm Systems
and NFPA
72 National
Fire Alarm and Signaling Code.
Refer to Application Bulletin P/N 3102483-EN for additional information
and cleaning instructions.
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal operating current
Alarm
51 µA
68 µA
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Rate-of-rise
15°F/min (9°C/min)
Air velocity [1]
0 to 4,000 ft./min (0 to 20.32 m/s)
Maximum spacing
for Heat Detectors
50 ft. (15.2 m) centers
Wall mount distance from
ceiling
12 in. (305 mm) max.
Compatible bases
Standard
Relay
Isolator
Audible
KI-SB, KI-SB4
KI-RB, KI-RB4
KI-IB, KI-IB4
KI-ABST, KI-ABDT, KI-ABLT
Compatible detector testers [2]
Testifire 1000, Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 100°F (0 to 38°C)
0 to 93% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
Environmental compensation
Automatic
[1] For duct installation, use a K-DMP duct detector mounting plate and
install per P/N 3102482-EN.
[2] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
Regulatory information
North American
standards
CAN/ULC-S529, CAN/ULC-S530, UL 268,
UL 268A, UL 521
UL/ULC smoke
sensitivity range
0.53 to 3.94 %/ft. (1.7 to 12.35 %/m) obscuration
UL/ULC fixed-
temperature alarm
rating
135°F (57.2°C)
UL/ULC Actual
alarm point
129 to 141°F (53.9 to 60.6°C)
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.kiddelifesafety.com.