background image

 

© 2020 Carrier 

1 / 4 

P/N 3102678-EN • REV 001 • ISS 02DEC20 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KIR-OSHCD Intelligent Rotary 
Multisensor Optical 
Photoelectric Smoke Heat and 
CO Detector Installation Sheet 

 

Description 

The KIR-OSHCD is an intelligent device that contains an advanced 
optical smoke sensor, a rate of rise heat sensor with a fixed 
temperature setting for detecting fire conditions, and a life safety 
carbon monoxide sensor to detect carbon monoxide gas from sources 
of combustion. The detector analyzes data from both the heat sensor 
and the optical sensing chamber to recognize smoke from a fire while 
ignoring nuisance non-fire sources and whether to initiate an alarm to 
the Fire Alarm Control Panel. The detector analyzes the smoke and 
heat sensors independently from the CO sensor to determine whether 
to initiate a fire alarm, a life safety CO alarm, or both. 

LED indicator. 

The LED indicator (see Figure 1) displays the following 

states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the area. 

Sensor end-of-life indicator. 

The detector signals a “COMMON 

TRBL ACT” condition on the control panel when the CO sensor 
reaches its end of life. Pressing the Details button on the control panel 
displays “END OF LIFE ACT” providing verification that it is an end-of-
life trouble of the CO sensor. This trouble remains active until the 
detector is replaced, even if the panel is reset.  

Figure 1: KIR-OSHCD features 

 

1. Self-locking 

tab 

2. LED 

indicator 

Installation  

Notes 

• 

This detector does not sense fires in areas where smoke or heat 
cannot reach the detector. Smoke or heat from fires in walls, roofs, 
or on the opposite side of closed doors may not reach the detector. 

• 

The heat sensor in this device provides a source of supplemental 
information. The heat sensor by itself does not provide life safety 
protection. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not install detectors until after final construction cleanup (unless 
otherwise specified by the AHJ). 

• 

Do not use smoke detectors with detector guards unless the 
combination has been evaluated and found suitable. 

• 

Install per NFPA 72 

National Fire Alarm and Signaling Code

NFPA 720 

Standard for the Installation of Carbon Monoxide (CO) 

Detection and Warning Equipment

, and UL 2075 

Standard for Gas 

and Vapor Detectors and Sensors

• 

Upon completion of the original installation and following any 
modifications or additions to the system, perform a calibrated 
sensitivity test per NFPA code. The Kidde Intelligent Series 
devices can perform this test and generate a system sensitivity 
report. 

To install the detector: 

1.  Install and wire the base as described on the installation sheet 

supplied with the base. 

2.  Set the detector address.  Refer to the panel technical reference 

manual for a list of valid addresses.  Use a screwdriver to adjust 
the two rotary switches on the back of the detector.   
(See Figure 1.)  Set the left rotary switch (0 through 12) for the 10s 
and 100s digit and the right rotary switch for the 0 through 9 digit. 

3.  Attach the detector to the base by rotating the detector clockwise 

until it snaps into the locked position. 

2

firealarmresources.com

Reviews: