To perform sensor function tests: 

1.  If desired, use the fire alarm control panel to put the detector or 

zone into a service group for testing. (Refer to the panel technical 
reference manual for instructions.) 

2.  Activate the smoke sensor using No Climb Products model Smoke 

Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol 
spray, a smoke generator, or the Testifire detector tester per the 
manufacturer’s instructions. 

3.  Activate the heat sensor using a hair dryer (maintaining a distance 

of three inches) or using a Testifire detector tester per the 
manufacturer’s instructions. 

Maintenance  

To ensure proper operation, plan maintenance (regular or selected) of 
the detector in accordance with the AHJ and all applicable governing 
laws, codes, or standards. Refer to CAN/ULC-S536 

Standard for the 

Inspection and Testing of Fire Alarm Systems

 and NFPA 

72 National 

Fire Alarm and Signaling Code.

 

Refer to Application Bulletin P/N 3102483-EN for additional information 
and cleaning instructions. 

Specifications 

 

Operating voltage 

15.20 to 19.95 VDC 

Current 
 

Normal operating current 

 

Alarm 

 
51 µA 
68 µA 

Vibration level 

10 to 35 Hz, with an amplitude of 
0.01 in. 

Rate-of-rise 

15°F/min (8°C/min) 

Air velocity [1] 

0 to 4,000 ft./min (0 to 20.32 m/s) 

Maximum spacing 
for Heat Detectors [3] 

50 ft. (15.2 m) centers 

Wall mount distance from 
ceiling 

12 in. (305 mm) max. 

Compatible bases  
 

Standard 

 

Relay 

 

Isolator 

 

Audible 

 
KI-SB, KI-SB4, GSA-SB, GSA-SB4 
KI-RB, KI-RB4, GSA-RB 
KI-IB, KI-IB4, GSA-IB, GSA-IB4 
KI-ABST, KI-ABDT, KI-ABLT 
GSA-SBT, GSA-AB4G 

Compatible detector testers [2] 

Testifire 1000, Testifire 2000 

Operating environment 
 

Temperature 

 

Relative humidity 

 
32 to 100°F (0 to 38°C) 
0 to 93% noncondensing 

Storage temperature 

−4 to 140°F (−20 to 60°C) 

Environmental compensation 

Automatic 

[1] For duct installation, use a K-DMP duct detector mounting plate and 
install per P/N 3102482-EN. 

[2] Requires the K-TSTSPACER Testifire adapter assembly. 

[3] When replacing GSA-HRS and GSA-HFS detectors with the  
KI-PHD, ensure that the spacing is 50 ft. (15.2 m) or less. 

 

Regulatory information 

 

North American 
standards 

CAN/ULC-S529, CAN/ULC-S530, UL 268, 
UL 268A, UL 521 

UL/ULC smoke 
sensitivity range 

0.53 to 3.94 %/ft. (1.7 to 12.35 %/m) obscuration 

UL/ULC fixed-
temperature alarm 
rating 

135°F (57.2°C) 

UL/ULC Actual 
alarm point 

129 to 141°F (53.9 to 60.6°C) 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

Industry Canada 
compliance 

This Class A digital apparatus complies with 
Canadian ICES-003. 

Contact information 

For contact information, see www.kiddelifesafety.com. 

Reviews: