background image

 

© 2018 United Technologies Corporation 

1 / 2 

P/N 3102466-

EN • REV 003 • ISS 31MAY18 

 

KI-PHD Intelligent Multisensor 
Photo-Heat Detector 
Installation Sheet 

 

Description 

The model KI-PHD Intelligent Multisensor Photo-Heat Detector is an 
intelligent device that contains a photoelectric smoke sensor and a 
rate-of-rise heat sensor with a fixed temperature setting. The detector 
analyzes the data from both sensing devices and determines whether 
an alarm should be initiated. Can be operated as a single detector 
using smoke or heat to initiate an alarm or as a split sensor with heat 
and smoke initiating separate signals. 

LED indicator. 

The LED indicator (see Figure 1 below) displays the 

following states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the area. 

Installation 

Notes

 

• 

This detector does not operate without electrical power. As fires 
frequently cause power interruption, discuss further safeguards 
with the local fire protection specialist. 

• 

This detector does not sense fires in areas where smoke or heat 
cannot reach the detector. Smoke or heat from fires in walls, roofs, 
or on the opposite side of closed doors may not reach the detector. 

• 

Photoelectric detectors have a wide range of sensing capabilities, 
and are best suited for detecting slow, smoldering fires. The heat 
sensor in this device provides a source of supplemental 
information. The heat sensor by itself does not provide life safety 
protection. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not use smoke detectors with detector guards unless the 
combination has been evaluated and found suitable. 

• 

In Canada, install according to the CAN/ULC-S524 

Standard for 

the Installation of Fire Alarm Systems,

 the CSA

 

C22.1 

Canadian 

Electrical Code

, and the local authority having jurisdiction. 

• 

Upon completion of the original installation and following any 
modifications or additions to the system, perform a calibrated 
sensitivity test per NFPA code. These devices can perform this test 
and the panel can generate a system sensitivity report. 

To install the device: 

1. 

Install and wire the base, as described on the installation sheet 
supplied with the base. 

2. 

Remove the serial number label from the detector and attach it to 
the project documentation. 

3. 

Attach the detector to the base by rotating the detector clockwise 
until it snaps into the locked position. 

Figure 1: KI-PHD features 

 

 
(1)  Self-locking tab 
(2)  LED indicator 

 

 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Test each sensor in the detector.  

Caution: 

Heat damage. Excessive heat may damage the detector 

outer cover. Do not apply excessive heat when using a hair dryer. 
When using a Testifire detector tester, you must install a Testifire 
Adapter Assembly. 

Make sure the Testifire Adapter Assembly (model K-TSTSPACER) is 
installed in the Testifire detector tester before testing. Refer to the 

Testifire Adapter Assembly Installation Sheet 

(P/N 3102495-ML) for 

further details. 

To perform an initial installation test: 

1.  Remove the detector from its base and verify that the proper 

detector address, trouble signals, and messages are reported. 

2.  For KI-PHD detectors placed in the air ducts, verify that the airflow 

is within specifications. See 

“Specifications” on page 2. 

3.  If wired for Class A operation, verify that the detector continues to 

operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4.  Place a momentary ground fault on the SLC circuit to verify 

operation of the ground fault detection circuitry. 

5.  Run a system detector sensitivity report on all detectors and verify 

that readings fall within acceptable limits. 

6.  Perform a sensor function test, as described below. 

(1)

(2)

Reviews: