background image

 

4 / 6 

 

P/N 3101069-EN • REV 005 • ISS 19OCT20 

Figure 6: Duct detector wiring 

 

(1)  Auxiliary equipment. Power-limited unless connected to a 

nonpower-limited source. If the source is nonpower-limited, 

eliminate the power-limited mark and maintain a minimum of 

0.25 in. (6.4 mm) space from power-limited wiring. For other 

mounting methods, see enclosure and bracket installation sheets 

to maintain separation of power-limited and nonpower-limited 

wiring. The wire size must be capable of handling fault current from 

the nonpower-limited source. 

 

— or — 

 

Use type FPL, FPLR, FPLP, or permitted substitute cables, 

ensuring that the power-limited cable conductors extending beyond 

the jacket are separated by a minimum of 0.25 in. (6.4 mm) space 

or by a nonconductive sleeve or nonconductive barrier from all 

other conductors. The wire size must be capable of handling fault 

current from the nonpower-limited source. Refer to NFPA 70 for 

more details. 

 

 

(2)  Remote alarm/active indicator. See “Specifications” on page 5 for a 

list of available model numbers. 

(3)  Connect only one remote test station or LED indicator to the 

detector. Wiring is unsupervised. Maximum wire resistance is 10 

Ω 

per wire. 

(4)  Remote test station. See “Specifications” on page 5 for a list of 

available model numbers. 

(5)  Power indicator. 

(6)  Alarm Indicator. 

(7)  JP3 (shown in the factory default position, for supervisory mode). 

(8)  Alarm position. 

(9)  Supervisory position. 

Testing 

Verifying the air pressure differential 

In order to verify air pressure differential, air must be moving through 

the HVAC system. 

To verify the air pressure differential: 

1.  Connect a suitable air pressure differential meter to the sampling 

tube and exhaust tube openings as shown in Figure 7. 

2.  Verify that the air pressure differential reading falls within the 

specified operating range of the detector. See “Specifications” on 

page 5. 

3.  If the air pressure differential measured does not fall within the 

specified operating range of the detector, make sure the sampling 

tube air holes are not obstructed and are facing the HVAC system 

airflow. 

(1)

(5)

(6)

(2) (3)

(3) (4)

JP3

(7)

(8)

(9)

firealarmresources.com

Reviews: