background image

© 2020 Carrier 

1 / 6 

P/N 3101069-EN • REV 005 • ISS 19OCT20 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX-PDD Duct Smoke 

Detector Installation Sheet 

 

Description 

The FX-PDD Duct Smoke Detector is designed for use in duct 

applications where temperatures can exceed standard detector 

capabilities. 
The device address is set using the two rotary switches located on 

the front of the unit. One device address is required. 
In installations where the controls and indicators are hidden from 

view, a remote test station or an LED indicator can be connected to 

the detector to provide these functions. 

Jumper settings 

The following jumper settings determine the operation of the 

detector. See Figure 6 for proper jumper location. 

Table 1: JP3 jumper settings 
Setting  

Description 

Alarm  

Configures the detector for alarm latching 

operation. 

Supervisory 

Configures the detector for supervisory 

operation. 

This is the factory default setting.  

LED operation 

Two LEDs, visible from the front of the detector, show its status. 

Table 2: LEDs 
LED 

Description 

Power LED 

Off when the detector is in the alarm state. 

Flashes intermittently when the detector is in 

the normal state. 

Alarm/active LED 

Indicates the detector is in the alarm/active 

state. 

Installation 

WARNINGS

 

•  The duct smoke detector is not intended as a substitute for open 

area protection. 

•  This detector does not operate without electrical power. As fires 

frequently cause power interruption, discuss further safeguards 

with the local fire protection specialist. 

•  The duct smoke detector does not operate as designed outside 

of the listed electrical and environmental specifications. 

•  The duct smoke detector does not sense smoke unless the 

ventilation system is operating and the sensor’s cover is 

properly installed. 

•  The duct smoke detector may not operate as designed unless 

installed in accordance with these instructions and all applicable 

national and local codes as determined by the local authority 

having jurisdiction. 

Note: 

Read these instructions thoroughly before installing. Refer to 

Application Bulletin P/N 3101107 for additional information regarding 

installation instructions. 

Installation guidelines 

To ensure correct operation, install the duct detector using the 

following guidelines: 
•  Install the duct smoke detector on a flat section of HVAC duct 

between six and ten duct widths from any bends or obstructions. 

•  Install supply-side detectors at a point downstream from the 

supply fan and after the air filter. 

•  Install return-side detectors at a point before the return air 

stream is diluted by outside air. 

Verifying the duct air velocity 

In order to verify the airflow direction and velocity, air must be 

moving through the HVAC system. 

To verify the duct air velocity: 

1.  Drill a small hole at the point where the duct smoke detector is 

being installed. 

2.  Using the SD-VTK Air Velocity Test Kit and a suitable air 

velocity meter, verify that the air velocity in the HVAC duct falls 

within the specified operating range of the detector and note 

which direction the air flows. 

3.  If the air velocity does not fall within the specified range, relocate 

the detector and seal the hole in the HVAC duct. Refer to 

Application Bulletin P/N 3101107 for additional information 

pertaining to installation locations. 

firealarmresources.com

Reviews: