background image

16

Testing

NOTE: WEEKLY TESTING IS REQUIRED!

CAUTION:  Due to the loudness (85 decibels) of the alarm,
always stand an arms length away from the unit when testing.

Test by pushing the Test button on the cover and hold it
down for a minimum of 2 seconds.  This will sound the
alarm if all the electronic circuitry, horn and battery are
working.  If no alarm sounds, check the fuse or circuit
breaker supplying power to the alarm circuit.  If the alarm
still does not sound, the unit has a defective battery or
some other failure.  DO NOT use an open flame to test
your alarm, you could damage the alarm or ignite
combustible materials and start a fire.

Test the alarm weekly to ensure proper operation.

Erratic

or low sound coming from your alarm may indicate a
defective alarm, and it should be returned for service (see

Warranty 

section).

Alarms failing an alarm test, or not operating normally,
must be replaced with a new alarm. Similarly, alarms more
than 10 years old must be replaced.

Alarm Removal

If the smoke alarm tamper resist feature has been
activated, refer to the 

Alarm Tamper Resist Feature

section

for removal instructions.

To remove the alarm from the mounting plate, rotate the
alarm in the direction of the "OFF" arrow on the cover. To
disconnect the AC Quick-Connect wire harness, squeeze
the locking arms on the sides of the Quick Connector
while pulling the connector away from the bottom of the
alarm (see Image 5).

M a i n t e n a n c e

M a i n t e n a n c e

15

Battery Replacement

Models

1275CA 

and

PE120CA

These alarms have a low/missing battery monitor circuit
which will cause the alarm to “chirp” approximately every
30-40 seconds for a minimum of seven (7) days when the
battery gets low.  Replace the battery when this condition
occurs.

Models 

1275CA

and 

PE120CA

use a 9 V carbon zinc

battery (alkaline and lithium batteries may also be used).
A fresh battery should last for one year under normal
operating conditions. 

Use only the following 9 volt batteries for replacement:

Carbon-Zinc Type

Eveready 216 or 1222 
Gold Peak 1604P or 1604S

Alkaline Type

Energizer 522
Duracell MN1604 or MX1604 
Gold Peak 1604A

Lithium Type

Ultralife U9VL-J

These batteries can be purchased at your local retailer.

WARNING!  Use only the batteries specified above.  Use of
different batteries than the recommended ones, may have a
detrimental effect on the smoke alarm.  A good safety measure is
to replace the battery at least once a year, or at the same time
you change your clocks for daylight saving time.   Be sure to
follow the battery installation instructions printed on the back of
the alarm.

NOTE:  WEEKLY TESTING IS REQUIRED!

NOTE:  For model

1275CA, 

if after battery replacement

the unit continues to chirp, wait for approximately 7
minutes.  The Hush® feature may have been activated
accidentally while changing the battery and will reset
automatically.

1235-7219-02_AC_MAN_ENG  10/5/04  4:36 PM  Page 14

Summary of Contents for 1235CA

Page 1: ...Smoke Alarm Manual 1235CA 1275CA PE120CA SINGLE AND OR MULTIPLE STATION SMOKE ALARM For alarm models ...

Page 2: ...m any regulatory requirements Do not try to repair the smoke alarm yourself Refer to the instructions in Warranty section for service WARNING Removal of the smoke alarm battery and disconnecting or loss of AC power will render the smoke alarm inoperative ELECTRICAL RATING 120 V AC 60 HZ 80 mA maximum per alarm maximum 80 mA for originating unit with 24 devices interconnected Installation 2 Introdu...

Page 3: ...ppliances are operated i e portable heaters or humidifiers Locate an alarm in every room where someone sleeps with the door closed The closed door may prevent the alarm from waking the sleeper Smoke heat and combustion products rise to the ceiling and spread horizontally Mounting the smoke alarm on the ceiling in the center of the room places it closest to all points in the room Ceiling mounting i...

Page 4: ...es may effect the sensitivity of the alarm Do not install in areas where the temperature is colder than 4 4 C 40 F or hotter than 37 8 C 100 F Do not install in areas where the relative humidity RH is greater than 85 Very humid areas with moisture or steam can cause nuisance alarms Avoid placing ionization smoke alarms in kitchen areas Normal cooking may cause nuisance alarms If a kitchen alarm is...

Page 5: ...HE RED WIRE TO ANYTHING Leave the red wire insulating cap in place to make certain that the red wire cannot contact any metal parts or the electrical box When alarms are interconnected all interconnected units must be powered from a single circuit A maximum of 24 Kidde devices may be interconnected in a multiple station arrangement The interconnect system should not exceed the NFPA interconnect li...

Page 6: ...tion Installation 10 9 IMAGE 3 IMAGE 4A IMAGE 4B ROTATE TO MOUNT OR TO REMOVE INTERCONNECT WIRING IMAGE 4C BATTERY REMINDER TAB IMAGE 4D TAMPER RESIST LOCKING PIN 1235 7219 02_AC_MAN_ENG 10 5 04 4 36 PM Page 8 ...

Page 7: ...ert it into the hole in the side of the alarm after the alarm has been installed on the mounting plate Image 4D NOTE The tamper resistant pin will have to be removed in order to change the battery models 1275CA and PE120CA Use long nose pliers to pull the pin out of the hole It is now possible to remove the alarm from the mounting plate Mounting CAUTION This unit is sealed The cover is not removab...

Page 8: ...moke is not too dense the alarm will silence immediately and chirp every 30 40 seconds for approximately 7 minutes This indicates that the alarm is in a temporarily desensitized condition The smoke alarm will automatically reset after approximately 7 minutes If after this period particles of combustion are still present the alarm will sound again NOTE Dense smoke will override the Hush control fea...

Page 9: ...Connector while pulling the connector away from the bottom of the alarm see Image 5 Maintenance Maintenance 15 Battery Replacement Models 1275CA and PE120CA These alarms have a low missing battery monitor circuit which will cause the alarm to chirp approximately every 30 40 seconds for a minimum of seven 7 days when the battery gets low Replace the battery when this condition occurs Models 1275CA ...

Page 10: ...Life safety from fire in residential occupancies is based primarily on early notification to occupants of the need to escape followed by the appropriate egress actions by those occupants Fire warning systems for dwelling units are capable of protecting about half of the occupants in potentially fatal fires Victims are often intimate with the fire too old or young or physically or mentally impaired...

Page 11: ...alarm installation Alarm Exit Procedure Alert small children in the home Leave immediately by your escape plan Every second counts so don t waste time getting dressed or picking up valuables In leaving don t open any inside door without first feeling its surface If hot or if you see smoke seeping through cracks don t open that door Instead use your alternate exit If the inside of the door is cool ...

Page 12: ... modified abused or altered after the date of purchase or if it fails to operate due to improper maintenance or inadequate AC or DC electrical power The liability of Kidde or any of its parent or subsidiary corporations arising from the sale of this smoke alarm or under the terms of this limited warranty shall not in any case exceed the cost of replacement of this smoke alarm and in no case shall ...

Reviews: